TIC-LF470B 

 

 

3

Communications output 

 

• HART (std.)

 

— 

Digital signal is superimposed on 

4–20mAdc current signal as follows: 
Conforms to HART protocol 
Load resistance: 240 to 750

 

Load capacitance: 0.25µF maximum 
Load inductance: 4mH maximum 

• PROFIBUS(opt.) 

Protocol: PROFIBUS-PA 
Baud rate: 31.25kbps 
Bus voltage: 9-30VDC 

Consumption electric current of bus: less than 16mA 

Manufacture Ident-No.: 093B

HEX 

Standard Ident-No.: 9740

HEX

 

Slave address: 0-126 (Default address is 126) 
Profile: Profile Ver.3.01 for Process Control 

Devices 

Function blocks: AI(Flow)

×

1 , Totalizer

×

1

 

LCD display: 

Full dot-matrix 128×128 dot LCD display 
(back–light provided) 
The data on the LCD inside the converter can rotate 
to 90, 180, and 270 degrees by a software, without 
rotating the indicator itself. (Combined type only) 

Parameter settings 

— Parameters can be set as 

follows: 

• IR Switches

: Three key switches are provided to 

set configuration parameters.   

• Digital communication

: The AF900 hand-held 

  terminal or PROFIBUS    is needed to set 

parameters.

 

• Zero adjustment: 

Zero point adjustment can be 

started by pressing the switch in the converter. 

• Damping: 

0.5 to 60 seconds (selectable in one 

second increments) 

“Field re-verification” 

Mag-Prover

 – Toshiba’s 

Zero span calibration tool allows unit to be 
re-calibrated and verified using an internal software 
program. (For more information contact Toshiba 
International Corp.) 

Conditions when power fails: 

Parameter setting values are stored in non–volatile 

memory and the values will be restored when the 

power returns to normal condition. The outputs and 

display will remain as follows when power fails.   

• Current output:    0mAdc 
• Digital output:   OFF 
• LCD display:    No display 
• PROFIBUS:    No communication 

Power supply: 

One of the following can be selected: 

• 100 to 240Vac, 50/60Hz (std.) 

(allowable voltage 80 to 264Vac) 

• 24Vdc (allowable voltage 18 to 36Vdc) 
• 110Vdc (allowable voltage 90 to 130Vdc) 

Surge protection:   

Arresters are installed in the power supply and a 
current signal output circuit to help protect the meter 
from lightning and improve personnel safety. 

Case: 

Aluminum alloy (equal to IP 67) 

Coating: 

Acrylic resin-baked coating, pearl

gray 

colored 

Cable connection port: 

Cable glands 

—  

Provided as standard, OD of 11 to 13mm   
Material Nylon 66 
G (PF) 1/2 male screws 

Applicable diameter 

   

0.433 to 0.512 inch (11 to 13mm) 

Note:

 When PROFIBUS option is specified, cable gland size is 

φ

6

8mm for signal cable, 

φ

11

13mm for power cable 

Vibration resistance: 

No resonance to the following levels of vibration:   

• 10 to 150Hz with acceleration of 9.8m/s

• Vibration of 30Hz with 29.4 m/s

in 4h in each 

direction will not cause any defect to unit.

 

Note:

 Avoid using the flowmeter in an environment with 

constant vibration. 

Dimensions :   

See Figure

 

MTBF: 

Converter: 220,000 hours (25 years) at 77 

°F

 (25 

°C

based on strict military specification 
MIL-HDBK-217F 

Detector: 350,000 hours (40 years) at 77 

°F

 (25 

°C

based on strict military specification 
MIL-HDBK-217F 

Содержание Electromagnetic Flowmeter LF470/LF612

Страница 1: ...icator can be used to communicate with the flowmeter from a remote place PROFIBUS PA 3 interface is available as an option 1 Please refer to the document TIC LF232 2 HARTprotocol Highway Addressable Remote Transducer is a communication protocol for industrial sensors recommended by the HCF HARTCommunication Foundation 3 PROFIBUS is the communication protocol for factory and process automation that...

Страница 2: ...for current and pulse outputs Zero adjustment Executes zero adjustment on stream at zero flow rate Output signals Current output 4 20mAdc load resistance 0 to 750Ω Note The current output cannot be used with the PROFIBUS PA communication Digital outputs One point std and one more point is optionally available as follows Digital output DO1 std Output type Transistor open collector Number of outputs...

Страница 3: ...nal Corp Conditions when power fails Parameter setting values are stored in non volatile memory and the values will be restored when the power returns to normal condition The outputs and display will remain as follows when power fails Current output 0mAdc Digital output OFF LCD display No display PROFIBUS No communication Power supply One of the following can be selected 100 to 240Vac 50 60Hz std ...

Страница 4: ...39 86 2 φ0 24 φ6 hole 4 φ0 20 φ5 hole Detector mounting plate 4mm thick Mountingscrews 1 18 30 1 57 40 Figure4 LF470 Mounting Board 矢視A 信号ケーブル グランド 電源ケーブルグランド 封止栓 励磁ケーブルグランド 電流出力ケーブルグランド 接地端子 M4 取付金具 4 φ 11 取付金具 82 36 156 13 151 178 200 151 74 0 3 25 LCD 表示器 赤外線スイッチ Excitation cable ground 5 94 151 5 94 151 2 91 74 4 φ0 43 φ11 Attachment LCD display 7 01 178 7 87 200 IR Switch Cable ground 6 14 15...

Страница 5: ...l input 20 30Vdc Power supply Instrument panel ordered separately Figure 6 Separate type LF470 LF612 flowmeters wiring Diagram Table 1 LF612 Converters Signal Table Symbol Description Cable L1 L2 Power supply Power cable CVV GND Ground for arrester FG Frame ground DI Digital Input 20 30Vdc DO1 Digital Output 1 DO2 Digital Output 2 COM Signal Common for DI DO1 DO2 Current Output 4 20mAdc or PROFIBU...

Страница 6: ...60 4 482 Table 3 Meter size and Flow Velocity US unit Unit L min Meter size mm 0 3m s 1m s 3m s 10m s 2 5 0 08835 0 2945 0 884 2 945 4 0 2262 0 7540 2 262 7 540 6 0 5088 1 6967 5 090 16 967 About establishment environment Do not store or install the flowmeter Where there is direct sunlight Where excessive vibration or mechanical shock occurs Where high temperature or high humidity conditions exist...

Страница 7: ...l chloride shock resistance Pt Ir for grounding plate H Hastelloy C Equivalent Packing used between main body and pipe connection adapter C Acid resistant ceramic D Alkali resistant ceramic G Ammonia resistance Mounting A Not provided B Provided 304 stainless steel Flow and calibration velocity range A 1 0 to 32 8 ft s standard range calibration B 1 0 to 32 8 ft s specified range calibration Cable...

Страница 8: ...ting BNP material SUS304 Accessory for pipe installation BNP material SUS304 1 2 Digital input output Digital output points 1 DO1 Digital output points 2 DO1 DO2 Digital input point 1 DI 1 2 Current output and Communication function Current output HART communication PROFIBUS communication Current output is not usable 1 2 3 Power supply 100Vac 240Vac 50 60Hz 24Vdc 110Vdc E Instruction manual Englis...

Отзывы: