– 4 –

Fresh-air inlet box

Installation Manual

EN

4

COMFIRMING THE INSTALLATION

After the installation completes, perform the test run to confirm that no abnormality is found.
For your future reference, please keep the installation manual on your side.

„

Duct connection and installation

CAUTION

• The outside air should be processed by the heat exchanger, etc.

(The outside air temperature range after processing: 54°F to 86°F (12°C to 30°C)

• Be sure to install the return duct.
• The duct fan for the outside air introduction shall require the interlock wiring.
• The sound insulation chamber shall be required to prevent from occurring the operating sound.
• The connection duct is not supplied with the product. Please procure Ø3.9” (100 mm) flexible duct on the market.

1

Mounting the connection duct

Set the flexible duct to the external side of the flange 
circle and fix it by using a band at 1” to 1.2” (25 to 30 
mm) position from the edge of the flexible duct.

2

Sealing the connection port

• Wrap the tightening band with the heat insulating 

materials of 0.79” (20 mm) thickness or more.

• Apply the adhesive tape around the heat insulating 

materials of the connection port to prevent the heat 
insulating materials from peeling off.

CAUTION

• Seal the connection port without any clearance to 

prevent from dew condensation.

• Keep the thermal insulation around the duct and the 

connection port.
(If the thermal insulation is not applied, the dew 
condensation may occur due to the temperature 
difference between the outside air and the air staying in 
the ceiling.)

Indoor unit

Flexible duct

Fresh-air inlet 
box

Tightening band

Fresh-air 
chamber

1” to 1.2” (25 t

o 30 mm)

Indoor unit

Fresh-air 
chamber

Tightening 
band

Adhesive tape

Flexible duct

Heat insulating materials 
(thickness: 0.79” (20 mm) or more)

Fresh-air inlet box

4-EN

+00EH99678601_01EN_FreshAirInletBox-IM.book  Page 4  Tuesday, December 8, 2009  2:03 PM

Содержание Carrier TCB-GB1602UUL

Страница 1: ...PLIT TYPE Fresh Air Inlet Box for 4 way Air Discharge Cassette Type Model name Fresh air inlet box TCB GB1602UUL Installation Manual Installation Manual Fresh air inlet box 1 English Manuel d installation Boîte d entrée d air frais 7 Français ...

Страница 2: ... require hospitalization or long term treatment as an outpatient 2 Physical damage indicates the damage relating to the property material CAUTION ON INSTALLATION WARNING Use TOSHIBA Carrier products for the parts sold separately Use the products specified by TOSHIBA Carrier for the parts sold separately such as the fresh air chamber ceiling panel etc The use of the products other than specified ma...

Страница 3: ...the 9 wire if a duct fan locally procured is installed 2 Attach the Fresh air chamber to the indoor unit For the details refer to the Fresh air chamber installation manual 3 Remove the shield plate for box from the Fresh air chamber Fig 1 4 Remove the shield plate assembly from the Fresh air chamber This part will be attached back later Fig 1 Indoor unit RAV SP 0UT UL Fresh air chamber TCB GFC1602...

Страница 4: ...0Attach back the shield plate assembly removed in 3 4 as it was installed 11Fix the wind shield 7 to the position where the suction grille is removed as shown in the Fig 3 with 2 mounting screws 4 If the wind shield is not fixed it is impossible to control the room temperature This may cause improper operation CAUTION Be sure to provide the opening for inspection on the Fresh air inlet box side Th...

Страница 5: ...ible duct to the external side of the flange circle and fix it by using a band at 1 to 1 2 25 to 30 mm position from the edge of the flexible duct 2 Sealing the connection port Wrap the tightening band with the heat insulating materials of 0 79 20 mm thickness or more Apply the adhesive tape around the heat insulating materials of the connection port to prevent the heat insulating materials from p...

Страница 6: ...hick line shows the connection circuit After installing the duct perform the test run to confirm whether the duct fan and the ventilation of the indoor unit work starting or stopping at the same timing For the test run following to the instructions described on the indoor unit installation manual Indoor unit Fresh air chamber Sound insulation chamber Duct fan Outside air filter Processed outside a...

Страница 7: ... 6 Fresh air inlet box Installation Manual EN MEMO ...

Страница 8: ...EH99678601 1 ...

Отзывы: