Fresh-air inlet box

Installation Manual

Thank you for purchasing the “Fresh-air inlet box” of TOSHIBA/Carrier Air Conditioner. Before starting the 
installation work, please read this manual carefully and install the product properly.

PRECAUTIONS FOR SAFETY

• Before installing the product, please read the “

PRECAUTIONS FOR SAFETY

” carefully to perform the proper 

installation.

• Be sure to keep the instructions described in the precautions for safety, since the descriptions include the 

important information for safety. The indication and the meaning of the symbols are as below.

*1 Bodily injury indicates injury, burns, electric shock, and other injuries which do not require hospitalization or 

long-term treatment as an outpatient.

*2

Physical damage indicates the damage relating to the property, material.

CAUTION ON INSTALLATION

WARNING

Use TOSHIBA/Carrier products for the parts sold separately.

Use the products specified by TOSHIBA/Carrier for the parts sold separately, such as the fresh-air chamber, ceiling 
panel, etc.
The use of the products other than specified may cause the water leakage, electric shock, fire, etc.

CAUTION

Turn off the earth leakage breaker when installing the fresh-air inlet box.
Be sure to attach the fresh-air inlet box to the fresh-air chamber.

Insufficient installation may cause the water leakage, electric shock, etc.

 WARNING

This sign denotes that serious injury may result from improper use.

 CAUTION

This sign denotes that the bodily injury*

 

or damage*

 

to property may result from improper use.

1

2

1-EN

+00EH99678601_01EN_FreshAirInletBox-IM.book  Page 1  Tuesday, December 8, 2009  2:03 PM

Содержание Carrier TCB-GB1602UUL

Страница 1: ...PLIT TYPE Fresh Air Inlet Box for 4 way Air Discharge Cassette Type Model name Fresh air inlet box TCB GB1602UUL Installation Manual Installation Manual Fresh air inlet box 1 English Manuel d installation Boîte d entrée d air frais 7 Français ...

Страница 2: ... require hospitalization or long term treatment as an outpatient 2 Physical damage indicates the damage relating to the property material CAUTION ON INSTALLATION WARNING Use TOSHIBA Carrier products for the parts sold separately Use the products specified by TOSHIBA Carrier for the parts sold separately such as the fresh air chamber ceiling panel etc The use of the products other than specified ma...

Страница 3: ...the 9 wire if a duct fan locally procured is installed 2 Attach the Fresh air chamber to the indoor unit For the details refer to the Fresh air chamber installation manual 3 Remove the shield plate for box from the Fresh air chamber Fig 1 4 Remove the shield plate assembly from the Fresh air chamber This part will be attached back later Fig 1 Indoor unit RAV SP 0UT UL Fresh air chamber TCB GFC1602...

Страница 4: ...0Attach back the shield plate assembly removed in 3 4 as it was installed 11Fix the wind shield 7 to the position where the suction grille is removed as shown in the Fig 3 with 2 mounting screws 4 If the wind shield is not fixed it is impossible to control the room temperature This may cause improper operation CAUTION Be sure to provide the opening for inspection on the Fresh air inlet box side Th...

Страница 5: ...ible duct to the external side of the flange circle and fix it by using a band at 1 to 1 2 25 to 30 mm position from the edge of the flexible duct 2 Sealing the connection port Wrap the tightening band with the heat insulating materials of 0 79 20 mm thickness or more Apply the adhesive tape around the heat insulating materials of the connection port to prevent the heat insulating materials from p...

Страница 6: ...hick line shows the connection circuit After installing the duct perform the test run to confirm whether the duct fan and the ventilation of the indoor unit work starting or stopping at the same timing For the test run following to the instructions described on the indoor unit installation manual Indoor unit Fresh air chamber Sound insulation chamber Duct fan Outside air filter Processed outside a...

Страница 7: ... 6 Fresh air inlet box Installation Manual EN MEMO ...