background image

12

     Packed valve handling precautions

•  Open the valve stem all the way out, but do not try to open it beyond the 

stopper.

•  Securely tighten the valve cap with torque in the following table:

Pipe size of Packed Valve

Size of Hexagon wrench

1/2 in. (12.7 mm and smallers)

A = 3/16 in. (4 mm)

Cap

Cap Size (H)

Torque

Valve Rod Cap

43/64 in. - 3/4 in.

(H17 - H19)

10 to 13 Ibf.ft

(14~18 N·m)

55/64 in. - 1-3/16 in.

(H22 - H30)

24 to 31 Ibf.ft

(33~42 N·m)

Service Port Cap

35/64 in.

(H14)

37 to 46 Ibf.ft

(50~62 N·m)

43/64 in.

(H17)

10 to 13 Ibf.ft

(14~18 N·m)

  

A

H

Hexagon wrench
is required.

Service Port Cap

Valve Rod Cap

OTHERS

OTHERS

Gas Leak Test

Test Operation

Troubleshooting (Check Point)

To switch the TEST RUN (COOL) mode, press RESET button for 10 seconds. 
(The beeper will make a short beep.)

Auto Restart Setting

The product was shipped with Auto Restart function in the ON position. 
Turn it OFF if this function is not required.

     

How to cancel the Auto Restart

Check the 

fl

 are nut 

connections for the 
gas leak with a gas 
leak detector or 
soap water.

This product is designed so that after a power failure it can restart 
automatically in the same operating mode as before the power failure.

1.  Press and hold the RESET button on the indoor unit for 3 seconds to 

cancel the operation. (3 beeps will sound but OPERATION lamp does not 
blink)

2.  Press and hold the RESET button on the indoor unit for 3 seconds to set 

the operation. (3 beeps will sound and OPERATION lamp blink 5 time/
sec for 5 seconds)

 

•  Do not operate ON timer and OFF timer.

Note :

  Default setting of auto restart operation is ON.

Check places with 

fl

 are nut connections

(indoor unit)

Check places for
the outdoor unit.

Valve cover

Information

RESET

RESET button

CAUTION

• 

5 IMPORTANT POINTS FOR PIPING WORK.

  (1)  Take away dust and moisture (inside of the connecting pipes).
  (2)  Tighten the connections (between pipes and unit).
  (3)  Evacuate the air in the connecting pipes using a VACUUM PUMP.
  (4)  Check gas leak (connected points).
  (5)  Be sure to fully open the packed valves before operation.
• 

UNIT DAMAGE HAZARD

  Failure to follow this caution may result in equipment damage or 

improper operation.

  Never use the system compressor as a vacuum pump.

The unit does not operate.

Cooling or Heating is abnormally low.

•  The power main switch is 

turned off.

•  The circuit breaker is tripped.
•  ON timer is set.

• The 

fi

 lters are blocked with dust.

•   The temperature has been set 

improperly.

•   Windows or doors are open.
•   The air inlet or outlet of the outdoor 

unit is blocked.

•   The fan speed is too low.
•   The operation mode is FAN or DRY.

1110651824-1 EN.indd   12

1110651824-1 EN.indd   12

11/13/13   2:02 PM

11/13/13   2:02 PM

Содержание Carrier RAS-15

Страница 1: ...FRANÇAIS Indoor unit RAS 15 17 22EK Series Outdoor unit RAS 15 17 22EA Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 1110651824 1 1110651824 1 EN indd 1 1110651824 1 EN indd 1 11 13 13 2 02 PM 11 13 13 2 02 PM ...

Страница 2: ...jo Eléctrico 7 UNIDAD INTERIOR 8 Situación de Instalación 8 Corte de un Orificio y Montaje de la Placa de Montaje 8 Conexión de Cables 9 Instalación la Tubería y el Tubo de Desagüe 9 Instalación de la Unidad Interior 10 Drenaje 11 Mando a distancia A B Selección 11 EVACUACIÓN 11 Evacuación 11 OTROS 12 Comprobación de Fugas 12 Prueba de Operación 12 Ajuste de Reinicio Automático 12 Troubleshooting ...

Страница 3: ... 4 6 35 Drain hose 19 11 16 0 5m Connecting pipe 15 5 16 0 39m Flare Ø1 2 12 70 For stud bold Ø2 1 4 6 8 15 32 215 5 Hanger Hanger Center line Installation plate outline Grille Inlet 2 7 8 73 5 2 7 8 73 5 Air outlet Hanger Hanger Hanger 10 5 16 262 5 10 5 16 262 5 Outline of indoor unit For stud bold Ø5 16 8 Ø13 32 10 10 9 278 7 9 200 8 7 222 7 9 200 5 9 150 20 7 525 5 2 132 1 9 16 47 6 1 32 154 4...

Страница 4: ...Detail A Rear Leg R7 32 R5 5 Ø1 4 Hole Ø6 Hole Ø1 4 Hole Ø6 Hole Ø7 16x9 16 Oval Hole Ø11x14 Oval Hole Detail B Front Leg COVER PACKED VALVE View Z WIRE GUARD View Z Liquid side Flare Nut Ø1 4 Ø6 35 Gas side Flare Nut Ø1 2 Ø12 7 Service Port Air Inlet Air Outlet 3 15 16 or more 100 mm or more 23 5 8 or more 600 mm or more 2 R7 32x43 64L R5 5x17L U Shape For Ø5 16 Ø13 32 Ø8 Ø10 Anchor Bolt 2 Ø7 16x...

Страница 5: ...components The power supply shall be connected to the outdoor unit by 3 wires The connecting cable between the indoor unit and outdoor unit needs to have 4 wires This cable provides the power for the indoor unit and the communication signal between the outdoor unit and indoor unit Consult local building codes NEC National Electrical Code or CEC Canadian Electrical Code for special requirements The...

Страница 6: ...IS MIXED WITH THE REFRIGERANT THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS IN THE EVENT OF REFRIGERANT LEAKAGE DURING INSTALLATION ALLOW FRESH AIR INTO THE ROOM IMMEDIATELY IF THE REFRIGERANT GAS IS HEATED BY FIRE OR OTHER MEAN IT GENERATES POISONOUS GAS Installing staring up and servicing air conditioning e...

Страница 7: ...t can sufficiently bear its weight If the load bearing of the unit is not enough or installation of the unit is improper the unit may fall and result in injury Electrical work must be performed by trained qualified installers and service mechanics in accordance with the code governing such installation work internal wiring regulations and the manual A dedicated circuit and the rated voltage must b...

Страница 8: ...ial polyethylene foam 5 16 in 8 mm thick 1 C Putty PVC tapes One each Field Supplied Installation Parts Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong winds Use Ø5 16 in Ø8 mm or Ø3 8 in Ø10 mm anchor bolts and nuts Fixing bolt arrangement of outdoor unit 4 1 4 in 108 mm 1 1 8 in 28 mm 4 15 16 in 125 mm Ø 1 in 2 5 m m Air inlet Air outlet 3 3 8 i...

Страница 9: ...oor unit from snow accumulation install a holding frame and attach a snow protection hood and plate Do not use a double stacked design Precautions about Installation in Regions with Snowfall and Cold Temperatures Snow protection plate Snow protection hood Snow accumulation line Holding frame At least 19 11 16 in 500 mm Install the unit at least 19 11 16 in 500 mm above the snow accumulation line A...

Страница 10: ... 9 1 6 in 6 5 m m 1 in 23 mm 5 in 132 mm 7 in 170 mm 2 in 50 mm 1 1 2 in 40 mm Stripping length of the Power supply cord and Interconnecting cable L1 L2 L1 L2 S Interconnecting cable Power supply cord Terminal block Unit inch mm L1 L2 L1 L2 S Ground line Connecting cable Power cord Ground line 3 8 10 3 8 10 1 3 16 30 2 12 16 70 3 8 10 3 8 10 1 3 16 30 1 9 16 40 Conduit plate Connector Lock nut Val...

Страница 11: ...itations Fig 2 Fig 1 Construction L1 L2 S L1 L2 S Cord clamp Terminal block Terminal cover Screw Ground line Screw Connecting cable Front panel Fig 3 Wiring CAUTION Failure to firmly install the unit may result in personal injury and property damage if the unit falls In case the unit is to be installed in a block brick concrete or similar type walls make 3 16 in 5 mm dia holes in the wall Insert c...

Страница 12: ...ch a case use the provided screws to fix the unit to the mounting plate Firmly insert the drain hose and drain cap otherwise water may leak In case of right or left piping After making slits of the front panel with a knife or a making off pin cut them with a pair of nippers or an equivalent tool In case of bottom right or bottom left piping After making slits of the front panel with a knife or a m...

Страница 13: ...ontrol with the tip of a pencil 00 will be shown on the display 4 Press MODE while pushing CHK B will show on the display and 00 will disappear and the air conditioner will turn OFF B is now memorized Note 1 Repeat above step to reset Remote Control back to A 2 Remote Control does not display A 3 Default setting of Remote Control from factory is A B Display 00 Display Evacuating After the piping h...

Страница 14: ...indoor unit for 3 seconds to cancel the operation 3 beeps will sound but OPERATION lamp does not blink 2 Press and hold the RESET button on the indoor unit for 3 seconds to set the operation 3 beeps will sound and OPERATION lamp blink 5 time sec for 5 seconds Do not operate ON timer and OFF timer Note Default setting of auto restart operation is ON Check places with flare nut connections indoor un...

Отзывы: