9.3 Object List
Object Object
Type
Instance
No.
‘Present Value’
Settings
Notes
On/Off (Setup)
Binary Output
1xxx01
Inactive:Off
Active:On
On/Off (State)
Binary Input
1xxx02
Inactive:Off
Active:On
Error Code
Analog Input
1xxx03
4 digit error code where
8000= ‘No Error’
6999= ‘Unit Not Present’
See
Appendix D
Operation Mode (Setup) Multi-State Output
1xxx04
01: Fan
02: Cool
03: Heat
04: Dry
05: Auto
06: N/A
07: Auto Cool
08: Auto Heat
Not
settable
09: Heat Exchange
10: VN-Auto
11: VN-Bypass
VN units
only
Operation Mode (State) Multi-State Input
1xxx05
01: Fan
02: Cool
03: Heat
04: Dry
05: Auto
06: N/A
07: Auto Cool
08: Auto Heat
09: Heat Exchange
10: VN-Auto
11: VN-Bypass
VN units
only
Fan Speed (Setup)
Multi-State Output
1xxx06
01: Low
02: Medium
03: High
04: Auto
Fan Speed (State)
Multi-State Input
1xxx07
01: Low
02: Medium
03: High
04: Auto
Room Temperature
Analog Input
1xxx08
Setpoint Temperature
(Setup)
Analog Output
1xxx09
18.0
o
C to 29.0
o
C
Setpoint Temperature
(State)
Analog Input
1xxx10
18.0
o
C to 29.0
o
C
Local Inhibit (Setup)
Binary Output
1xxx11
Inactive:Off
Active:Inhibit
Local Inhibit (State)
Binary Input
1xxx12
Inactive:Off
Active:Inhibited