72
Analog I/O Modules (AD268 / DA264 / TC218)
5. I/O Allocation and Programming
PART 3 TC218
Thermocouple (type J) input:
A/D conversion data
Input
temperature
Hexadecimal
Integer
Resolution
Burnout detection
-
H7FFF
32767
Upper limit
+1200
°
C
H5DC0
24000
:
:
:
Full scale (positive)
+800
°
C
H3E80
16000
:
:
:
+0.05
°
C
H0001
1
0
0 V
H0000
0
-0.05
°
C
HFFFF
-1
:
:
:
Full scale (negative)
-200
°
C
HF060
-4000
:
:
:
Lower limit
-210
°
C
HEF98
-4200
0.05
°
C / bit
D = 20
×
A
D: Digital data
A: Temperature (
°
C)
0
Temperature
HF060
-4000
Digital vale
-200
°
C
Upper limit
+800
°
C
H3E80
16000
Lower limit
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]