5

Piping and Drain Hose Installation

*  Since dewing results in a machine trouble, make sure to insulate both 

connecting pipes. (Use polyethylene foam as insulating material.)

     

Piping and drain hose forming

1.  Die-cutting front panel slit

 

Cut out the slit on the leftward or right side of the front panel for the left 
or right connection and the slit on the bottom left or right side of the front 
panel for the bottom left or right connection with a pair of nippers.

2.  Changing drain hose

 

For leftward connection, bottom-leftward connection and rearleftward 
connection’s piping, it is necessary to change the drain hose and drain 
cap.

How to remove the drain cap

Clip the drain cap by needle-
nose pliers and pull out.

How to remove the drain hose

•  The drain hose can be removed by removing the 

screw securing the drain hose and then pulling out 
the drain hose.

•  When removing the drain hose, be careful of any 

sharp edges of steel plate. The edges can injuries.

•  To install the drain hose, insert the drain hose 

fi

 rmly until the connection part contacts with heat 

insulator, and the secure it with original screw.

How to 

fi

 x the drain cap

1) Insert hexagon 
 

wrench (4 mm) 

 

in a center head.

2)  Firmly insert the drain cap.

Firmly insert the drain hose and drain cap; otherwise, water may leak.

In case of right or left piping

•  After scribing slits of the front panel with a 

knife or a making-off pin, cut them with a 
pair of nippers or an equivalent tool. 

In case of bottom right or bottom left piping

•  After scribing slits of the front panel with a 

knife or a making-off pin, cut them with a 
pair of nippers or an equivalent tool. 

Left-hand connection with piping

•  Bend the connecting pipe so that it is laid within 43 mm above the wall 

surface. If the connecting pipe is laid exceeding 43 mm above the wall 
surface, the indoor unit may unstably be set on the wall.

  When bending the connecting pipe, make sure to use a spring bender so as 

not to crush the pipe.

Bend the connecting pipe within a radius of 30 mm.

To connect the pipe after installation of the unit (

fi

 gure)

How to install the air inlet grille on the indoor 
unit

•  When attaching the air inlet grille, 

perform the same process as for 
removal but in reverse order.

  

Wiring Connection

Wiring of the connecting cable can be carried out without removing the 
front panel.

1.  Remove the air inlet grille.
 

Open the air inlet grille upward and pull it toward you.

2.  Remove the terminal cover and cord clamp.
3.  Insert the connecting cable (according to the local rule) into the pipe hole 

on the wall.

4.  Take out the connecting cable through the cable slot on the rear panel so 

that it protrudes about 15 cm from the front.

5.  Insert the connecting cable fully into the terminal block and secure it tightly 

with screws.

6.  Tightening torque : 1.2 N·m (0.12 kgf·m)
7.  Secure the connecting cable with the cord clamp.
8.  Fix the terminal cover, rear plate bushing and air inlet grille on the indoor 

unit.

     

How to connect the connecting cable

•  Be sure to refer to the wiring system diagram labeled inside the front 

panel.

•  Check local electrical cords and also any speci

fi

 c wiring instructions or 

limitations. 

 

NOTE

•  Use stranded wire only.
•  Wire type : H07RN-F or more

CAUTION

CAUTION

1

2

3

Cord clamp

Terminal block

Terminal cover

Screw

Earth line

Screw

Connecting cable

Earth line

Connecting cable

Stripping length of the connecting cable

about 15 cm

80

Liquid side

Gas side

(To the forefront of 

fl

 are)

Outward form of indoor unit

R 30 mm (Use polisin (polyethylene)
core or the like for bending pipe.)

Use the handle of screwdriver, etc.

Rear right

Rear left

Bottom left

Left

Bottom right

Right

Die-cutting

front panel slit

Changing

drain hose

Piping preparation

Heat insulator

Drain hose

4 mm

No gap

Do not apply lubricating oil
(refrigerant machine oil) when
inserting the drain cap. Application
causes deterioration and drain
leakage from the plug.

Insert a hexagon
wrench (4 mm).

Slit

Slit

520 mm

420 mm

43 mm

110 mm

80 mm

20 mm

10 mm

1110651154-EN.indd   5

1110651154-EN.indd   5

2/15/10   9:39:39 AM

2/15/10   9:39:39 AM

Содержание 22SAV

Страница 1: ...r unit RAS 18 22SKV R Series Outdoor unit RAS 18 22SAV Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 1110651154 Cover 1110651154 indd 1 Cover 1110651154 indd 1 1 22 10 11 14 26 AM 1 22 10 11 14 26 AM ...

Страница 2: ...Installation 5 n Indoor Unit Fixing 6 n Drainage 6 OUTDOOR UNIT 6 n Installation Place 6 n Precautions about Installation in Regions with Snowfall and Cold Temperatures 6 n Refrigerant Piping Connection 7 n Evacuating 7 n Wiring Connection 7 n Electrical Work 7 OTHERS 8 n Gas Leak Test 8 n Remote Control A B Selection 8 n Test Operation 8 n Auto Restart Setting 8 Cover 1110651154 indd 2 Cover 1110...

Страница 3: ...ing in damage to the unit or injury Do not modify the power cable connect the cable midway or use a multiple outlet extension cable Doing so may cause contact failure insulation failure or excess current resulting in fire or electrical shock If you detect any damage do not install the unit Contact your supplying dealer immediately New refrigerant air conditioner installation CAUTION THIS AIR CONDI...

Страница 4: ...use electrical shock Follow the instructions in this installation manual to arrange the drain pipe for proper drainage from the unit Ensure that drained water is discharged Improper drainage can result in water leakage causing water damage to furniture Tighten the flare nut with a torque wrench using the prescribed method Do not apply excess torque Otherwise the nut may crack after a long period o...

Страница 5: ...rain hose to get slack Cut the piping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 8 mm thick heat resisting polyethylene foam 1 Batteries Pan head wood screw Remote control holder Vinyl tape Apply after carrying out a drainage test Wireless remote control Saddl...

Страница 6: ...he pipe hole dia 65 mm at a slight downward slant to the outdoor side A place which provides the spaces around the indoor unit as shown in the diagram A place where there are no obstacles near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installed as top of the indoor uni...

Страница 7: ...pipe make sure to use a spring bender so as not to crush the pipe Bend the connecting pipe within a radius of 30 mm To connect the pipe after installation of the unit figure How to install the air inlet grille on the indoor unit When attaching the air inlet grille perform the same process as for removal but in reverse order Wiring Connection Wiring of the connecting cable can be carried out withou...

Страница 8: ...cause any problems CAUTION 1 Install the outdoor unit in a location where there are no obstructions near its air intake or air outlet 2 When the outdoor unit is installed in a place that is always exposed to strong winds like on the coast or on a high story of a building secure the normal fan operation using a duct or a wind shield 3 Especially in windy areas install the unit to prevent the admiss...

Страница 9: ...uid side Service port Valve core Setting pin Packed valve at gas side Vacuum pump Vacuum pump adapter for counter flow prevention For R410A only Charge hose For R410A only Handle Hi Keep full closed Manifold valve Pressure gauge Compound pressure gauge Handle Lo Charge hose For R410A only Connecting pipe 101 kPa 76 cmHg Open the valve stem until it touches the stopper Once it is in contact with th...

Страница 10: ...ns for the gas leak with a gas leak detector or soap water This product is designed so that after a power failure it can restart automatically in the same operating mode as before the power failure 1 Press and hold the RESET button on the indoor unit for 3 seconds to set the operation 3 beep sound and OPERATION lamp blink 5 time sec for 5 seconds 2 Press and hold the RESET button on the indoor uni...

Страница 11: ...Cover back 1110651154 indd 1 Cover back 1110651154 indd 1 1 22 10 11 15 21 AM 1 22 10 11 15 21 AM ...

Страница 12: ...Cover back 1110651154 indd 2 Cover back 1110651154 indd 2 1 22 10 11 15 22 AM 1 22 10 11 15 22 AM ...

Отзывы: