TOSHIBA
CONSERVER CES INSTRUCTIONS
1-2
INSTRUCTIONS IMPORTANTES CONCERNANT LA SÉCURITÉ
Cette notice contient des
instructions importantes concernant
la sécurité.
Un battery puet présenter un risque de choc électrique, de brûlure par
transfert d' énergie.
Por le replacement, utiliser le même nombre de batteries du modéle
suivant.
L' élimination des batteries est règlementèe. Consultar les codes
locaux à cet effet.
ATTENTION
ATTENTION
© Copyright 1994
ATTENTION
DANGER
IMPORTANT SAFETY INSTRUCTIONS
Proper maintenance to the battery system of this unit must be done by a
qualified service techincian, this is essential to the safety and reliability of
your UPS system. Refer to service manual.
A battery can present a risk of electrical shock and high short
circuit current.
The following precautions should be observed when
working with batteries:
1) Verify that the UPS is off and that the power cord is disconnected from the power source.
2) Remove watches, rings or other metal objects.
3) Use tools with insulated handles to prevent inadvertent shorts.
4) Wear rubber gloves and boots.
5) Do not lay tools or metal parts on top of batteries.
6) Determine if the battery is inadvertently grounded. If inadvertently grounded, remove
source of ground.
Contact with any part of a grounded battery can result in
electrical shock.
The likelihood of such shock will be reduced if such grounds are
removed during installation and maintenance.
7) Verify circuit polarities prior to making connections.
8) Disconnect charging source and load proir to connecting or diconnecting terminals.
9) VRLA batteries contain an explosive mixture of hydrogen gas. Do not smoke, cause a flame
or spark in the immediate area of the batteries. This includes static electricity from the body.
10) Do not attempt to open the batteries in order to add water or sample the specific gravity of the
electrolyte. The batteries are valve regulated lead acid type and such servicing is not
possible without damaging the battery.
11) Use proper lifting means when moving batteries and wear all appropriate safety clothing and
equipment.
12) Do not dispose of lead acid batteries except through channels in accordance with local, state
and federal regulations.
WARNING
Model Capacity
Manufacturer
Type
Quantity
UC3-BC-0230
Yuasa
NP7-12FR
8
UC3-BC-0260
24
UC3-BC-0330
12
UC3-BC-0360
36
UC3-BC-0630
18
UC3-BC-0660
54
UC3-BC-0830
42