background image

Command Interpreter (send radio commands to a specific WOB):

•  Used to set flow mode parameters on WOB and for general testing of communications and flow.
•  To send a command to a board, connect XTEND serial radio to laptop, and launch a terminal program (hypertrm is 

installed Windows XP). Set to 19200 baud with no flow control (19200 N81). You may find it easier to create a .txt file 

with the desired commands, and then use hypertrm Transfer menu -> Send text File to send the commands to the radio. 

It is also possible to type commands directly into hypertrm but note that a delay between characters or commands will 

cause the command to fail.

All commands Start with ATaaaaabb where:

aaaaa is the board precode (typically 00 followed by the three digit address of the master unit)

bb is the board number on the address switch. ( A=10,B=11,C=12,D=13,E=14, and F = 15 )

To test communication:

Send: ATaaaaabb

Response: aaaaa:bb->WOB ver:0.51 (or current version)

To read k factor:

Send: ATaaaaabbKc?  

(where c is the flow input number (1, or 2)

Response: aaaaa:bb->Kc = <K setting here>

To set k factor:

Send: ATaaaaabbKc=ddd.ddd 

(where ddd.ddd is desired k factor  

padded with zeros)

Response: aaaaa:bb->Kc Set

To read offset:

Send: ATaaaaabbOc?

Response: aaaaa:bb->Kc = <offset setting here>

To set positive offset:

Send: ATaaaaabbOc=e.eee 

(where e.eee is offset factor  

padded with zeros)

Response: aaaaa:bb->Oc Set

To set negative offset:

Send: ATaaaaabbOc=-e.eee

(where e.eee is offset factor padded with zeros)

Response: aaaaa:bb->Oc Set

To read flow mode:

Send: ATaaaaabbM?

Response: aaaaa:bb-> <flow mode 1+2 or 1-2 will be indicated here>

To set flow mode:

Send: ATaaaaabbM=f  

(where f = 0 for additive (1+2) or  

f = 1 for difference (1-2)

Response: aaaaa:bb->Flow Mode Set

To read flow data:

Send: ATaaaaabbF?

Response: <several lines of flow data showing channel 1, channel 2, 

and combined results>

Содержание DXi

Страница 1: ...iverside California Approx Weight 0 08 lbs OriginatingLocation Riverside Page count 8 Sheet count 4 Release Change Authorization Number 5174342 Printing instructions gray scale See subsequent pages for original PDF REVISION SHEET Rev ECM No Description ofChange Drafter Date Approved By A 5174342 Release to rev A Richard Keightley 11 8 2021 Shankara Raghuraman ...

Страница 2: ... a wall stud If installing the controller on masonry or drywall use the appropriate type screw anchors and fasteners 2 Install the screw anchors at 83 4 22 23cm A on center Caution All cabinet openings required for installation and wiring are provided Drilling or cutting through the cabinet should be avoided Metal chips and filings entering the cabinet can damage internal components 3 Install the ...

Страница 3: ...LINE AND NEUTRAL POLES ENSURE THE AC POWER SOURCE IS OFF PRIOR TO SERVICING FAILURE TO COMPLY MAY RESULT IN SERIOUS INJURY DUE TO ELECTRICAL SHOCK HAZARD 1 Ensure the power is disconnected at the source See Warning above 2 Remove the terminal block cover located below the transformer 3 Route the AC power and equipment ground wires through electrical conduit into the controller 4 Strip wire ends to...

Страница 4: ... the controller The top of the ground rod should be buried approximately 12 30 5cm below grade 2 Route a 6 AWG 13 0mm2 solid copper wire connected to the earth ground device into the controller cabinet through the access hole provided below the copper ground lug Insert and secure the copper wire to the ground lug To provide the most efficient path to earth ground route the ground wire between the ...

Страница 5: ... each wire 3 Connect the valve common wire s to terminal marked VC COM 4 Connect each valve power wire to the appropriate station number terminal See Figure 5 5 Pull lightly on each wire to confirm positive retention 6 Ensure all exposed wiring inside the controller is taped back and properly insulated 7 To release depress the small tab nearest the wire using a small blade screwdriver Output Switc...

Страница 6: ...om of the WOB One terminal is marked FLOW1 the other FLOW2 see Figure 8 Caution To prevent damage to the controller and or sensor equipment turn off power to the controller prior to connecting sensor wires Installation Notes The ALARM terminal is not used The sensor connection terminals accept 16 28 AWG 1 5mm2 0 08mm2 solid core copper wire To enable positive wire retention insulation must be remo...

Страница 7: ... switch Once a board is in Training Mode the next WOB communication it detects will cause the precode in the communication to be learned so that from that point forward the board will only listen to communications with that precode This allows multiple DXi controllers to run WOBs with the same board numbers within radio range since each WOB only listens to the precode of its master Once a board is...

Страница 8: ... switch A 10 B 11 C 12 D 13 E 14 and F 15 To test communication Send ATaaaaabb Response aaaaa bb WOB ver 0 51 or current version To read k factor Send ATaaaaabbKc where c is the flow input number 1 or 2 Response aaaaa bb Kc K setting here To set k factor Send ATaaaaabbKc ddd ddd where ddd ddd is desired k factor padded with zeros Response aaaaa bb Kc Set To read offset Send ATaaaaabbOc Response aa...

Страница 9: ...se contenu dans le présent appareil est conforme aux CNR d innovation Science et Dévellopement économique Canada applicables aux appareils radio exempts de licence L exploitation est autorisée aux deux condtions suivantes 1 l appareil ne doit pas produire de brouillage et 2 l appareil doit accepter tout brouillage radioélectrique subi même si le brouillage est suceptible d en compromettre le fonct...

Отзывы: