23
Home (Membrane button)
Home
The home page displays all controller statuses and important values of the controller. All voltages, currents,
pressure, motor state and status, as well as all timers and motor starting sequences.
The entire background will become red if an alarm becomes active. This feature will help the user identify a problem
even from a significant distance away from the controller.
A: Navigation bar which contains general information about:
- The language (the language may be changed by pressing on it)
- The page title
- The alarm banner (warning and alarm messages may be shown)
- The date and time (adjustable in the Configuration page)
- The temperature. It can be changed to Celsius or Fahrenheit by pressing on it.
B: Normal power voltage. Each box represents an individual phase voltage between the two adjacent lines.
C: Alternate power voltage. Each box represents an individual phase voltage between the two adjacent lines.
D: The transfer switch position is represented here by the form of contactors switching the desired power lines.
E: Current. Each box represents an individual phase current between the two adjacent lines.
F: Motor contactors. An animation shows the contactor opened or closed depending on the signal sent to the main
coil.
G: The electric motor. It will be grey if the engine is stopped, green if a “Motor Run” signal is detected and red if a
“Fail to start” occurred. Pressing on the engine will redirect the user to the “Last Service Statistics” page, which
monitors all relevant statistics concerning the controller since the last service.
H: Timers. Sequential start timer (on-delay) will start counting upon a pressure drop. The motor will only start if the
pressure is still below the start point after the expiration of this timer. The minimum run period timer (off
–delay) for
automatic shutdown will start counting once the stop pressure is reached. The pump will stop at the expiration of
this timer if the pressure is still above the stop pressure. If a periodic test has been programmed, the remaining time
will be displayed. If a manual run test has been energized, the remaining time will be displayed.
Home
Содержание GPU
Страница 20: ...20 The First Start up is now completed The controller is fully installed and configured ...
Страница 45: ...45 The Sensors Pages ...
Страница 52: ...52 ...
Страница 67: ...67 ...