background image

TORK

DIGITAL TIME SWITCH

DRY CONTACT RATINGS

30A

30A

  6A

  5A

470VA

2 HP

12A

12A

  6A

  5A

690VA

Type

 of Load

120

VAC

240

VAC

277

VAC

20A Resistive @ 28VDC

Resistive

Inductive

Ballast

Tungsten

Pilot Duty

Motor

30A

30A

20A

  5A

470VA

1 HP

3

SPST

4

LOAD

S

1

2

N

L

N

TIMER

SUPPLY

EW101

120VAC

EW101-2

240VAC

EW101-3

277VAC

EW101-24 

24VAC

OUTPUT: SPST

DPST

TIMER

SUPPLY

3

5

6

4

L

L

N

1

2

LOAD

N

LOAD

N

EW103

120VAC

EW103-2

240VAC

EW103-3

277VAC

EW103-24 

24VAC

OUTPUT: DPST

DRY CONTACT RATINGS

Resistive

Inductive

Ballast

Tungsten

Pilot Duty

Motor

20A

20A

  6A

  5A

1 HP

Type

of Load

120VAC

240VAC

277VAC

N.O.   20A Resistive @ 28VDC

N.O.     N.C

N.O.    N.C

N.O.    N.C

470

VA

10A

10A

 3A

  3A

275

VA

20A

20A

  6A

  5A

2 HP

470

VA

10A

10A

  3A

  3A

275

VA

 6A

 6A

 6A

  –

690

VA

3A

 3A

 3A

  –

1/4

HP

1/2

HP

N.C.   10A Resistive @ 28VDC

TIMER

SUPPLY

3

4

5

SPDT

1

2

L

N

LOAD

LOAD

N

N

EW120

120VAC

EW120-2

240VAC

EW120-3

277VAC

EW120-24 

24VAC

OUTPUT: SPDT

TORK

®

MLI-140(B)

1 GROVE STREET, MT. VERNON, NY 10550  TEL: 914-664-3542

FAX: 914-664-5052

Disconnect power at main panel prior to installing or servicing this time
switch or the equipment  connected to it.
Install and use in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 10-16) suitable for 75
degrees C (167 degrees F). Use copper wire only.

Replace insulator before turning on electricity.