Toptech TT-HUM-365 Скачать руководство пользователя страница 5

POWERED FLOW-THROUGH HUMIDIFIER

5

68-3074—01

MAINTENANCE

A regular maintenance program prolongs the life of the 

humidifier and provides a more comfortable environment. 

Frequency of cleanings depends on water conditions.

Either hard or soft water can be used in the humidifier, but hard 

water mineral deposits are more difficult to clean then soft 

water deposits.

Use the following procedure to clean the humidifier.

CAUTION

Personal Injury or Equipment Hazard.

Power Supply can cause electrical shock or 

equipment damage.

Disconnect power supply before performing humidifier 

maintenance.

IMPORTANT

Never oil any part of the humidifier.

Every 1 To 3 Months
(Depending on Water Quality)

1.

Disconnect the power and turn off the humidifier water 

supply.

2.

Remove the humidifier cover. See Fig. 9.

Fig. 9. Location of humidifier parts.

3.

Remove the humidifier pad assembly from the humidifier 

by grasping the tray and pulling it toward you.

4.

Pull one side of the humidifier pad assembly frame 

toward you and remove the tray from the frame.

5.

Gently pinch the water nozzle catches inward until the 

water nozzle can be lifted off the tray.

6.

Slide the humidifier pad out of the frame.

7.

Carefully scrape any mineral deposits from the tray and 

frame. Be sure the frame drain hole has nothing blocking 

it.

8.

Check the humidifier pad and if excessive mineral 

deposits are present, replace with a new HC26E Antimi-

crobial Pad.

9.

Disconnect the drain hose from the drain fitting on the 

bottom of the humidifier housing.

10.

Clean the drain fitting, if necessary.

11.

Bend the drain hose to loosen any mineral deposits.

12.

Flush the drain hose with pressurized water (a running 

tap) to clean the hose.

13.

Reattach the drain hose to the drain fitting.

14.

Slide the humidifier pad back into the frame.

IMPORTANT

To maintain the antimicrobial properties of the humidi-

fier, use only an HC26E Antimicrobial Pad. Be sure 

the marked side of the antimicrobial humidifier pad is 

facing up for proper performance.

15.

Reattach the tray to the frame.

16.

 Snap the water nozzle back on the tray.

17.

 Place the antimicrobial humidifier pad assembly in the 

humidifier housing and press until the assembly is 

seated.

18.

Be sure the water feed tube is placed in the guide slots 

of the humidifier housing.

19.

Replace the humidifier cover.

20.

Verify the humidifier operation by following the steps in 

the Checkout Procedure section.

End of Humidification Season

The humidifier needs to be cleaned and shut off at the end of 

the heating season. Follow steps 1 through 19 from the Every 

1 To 3 Months section.

IMPORTANT

Be sure the humidifier power is off.

Beginning of Humidification Season

Refer to the Checkout Procedure section for complete 

humidifier startup instructions.

Vacation

Turn off the humidifier water supply and the humidity control 

while on vacation. When you return, turn on the humidifier 

water supply and reset the humidity control to restart the 

humidifier.

Table 1. Recommended Humidity Control Settings.

Outside Temperature

Recommended Setting

Outside Temperature

Recommended Setting

-20°F (-29°C)

15

+10°F (-12°C)

30

-10°F (-23°C)

20

+20°F (-7°C)

35

0°F (-18°C)

25

+20°F (-7°C)

40

M28929

COVER 

ASSEMBLY

HUMIDIFIER 

PAD ASSEMBLY

FEED TUBE NOZZLE

WATER 

DISTRIBUTION TRAY

HUMIDIFIER

HOUSING

THUMB 

SCREW

Содержание TT-HUM-365

Страница 1: ...T The specifications given in this publication do not include normal manufacturing tolerances Therefore this unit may not exactly match the listed specifica tions Also this product is tested and calib...

Страница 2: ...ure is between 32 F 0 C and 160 F 71 C Do not install where freezing temperatures could occur Be sure supply plenum static pressure is no greater than 0 4 in wc and water pressure is no greater than 1...

Страница 3: ...with applicable local codes ordinances and regulations For Convertible Humidity Control Wiring Connections IMPORTANT Select models of fan centers include humidifier taps so the current sensing relay o...

Страница 4: ...the Convertible Humidity Control The convertible humidity control is installed either on an interior wall in the living area or on the return air duct Choose the humidity control setting using the com...

Страница 5: ...ing if necessary 11 Bend the drain hose to loosen any mineral deposits 12 Flush the drain hose with pressurized water a running tap to clean the hose 13 Reattach the drain hose to the drain fitting 14...

Страница 6: ...ower is on Check all external wiring connections Check the humidity control setting Call a professional heating contractor Rapid air changes Drafts cold air is dry and is an added load to the humidifi...

Страница 7: ...POWERED FLOW THROUGH HUMIDIFIER 7 68 3074 01 Fig 10 Key to Replacement Parts 1 M28931 2 5 3 6 4...

Страница 8: ...POWERED FLOW THROUGH HUMIDIFIER U S Registered Trademark 2010 68 3074 01 M S 08 10 Printed in U S A...

Отзывы: