18
AC Powered Models
3.6.1
Provide over current protection using a 15 Amp circuit breaker or equivalent. The breaker also serves
as a means of disconnection from the operating supply as required by UL/ISA/IEC 61010-1 and
CAN/CSA-C22.2 NO. 61010-1. The disconnected device may not be blocked or be made difficult to
operate by the MultiLoad II/ RCU II or any other device. Note that installation of disconnects are
typically prohibited in Class I, Division 2 locations.
Power required: 85
– 250 Vac, 47 – 63 Hz, 300 mA @ 85Vac/ 150 mA @250Vac. The power
connector is located in the right hand, bottom corner of the Power Supply/Communication board as
shown in figure 3.3. Select supply wire rated 300V or better with a flammability rating of at least VW-1.
Figure 3.3
MultiLoad II/ RCU II AC Power Supply/Comm Board
DC Powered Models
3.6.2
The MultiLoad II/ and RCU II is optionally available with a 24 Vdc power supply. The power source
used to supply the MutliLoad II/RCUII must be rated 9
– 30 Vdc SELV, Limited Energy (Class 2). The
rated supply input current is 600mA. The supply should be protected by a 1.5 Amp
fuse.
Содержание MultiLoad II DIV-2
Страница 1: ...MultiLoad II RCU II DIVISION 2 DIV2 Installation Guide Part 6074...
Страница 7: ...Hardware Revision 80 9 1 Manual Revision 81 9 2...
Страница 18: ...9 2 1 2 2 Back View Figure 2 3 Unit Outline Drawing Back View RCUII ML II Div 2 MOUNTING TEMPLATE...
Страница 20: ...11 2 1 2 4 Side View Figure 2 6 Unit Outline Drawing Side View...
Страница 25: ...16 Figure 3 1 Suggested Mounting Position Figure 3 2 Screen Visible Area...
Страница 59: ...50 Typical 1 Meter Application Wiring Example IP E Drawing Electrical Wiring Schedule 5 4 14...
Страница 64: ...55...
Страница 73: ...64...
Страница 88: ...79 Chapter8 HardwareRevisionHistory Compatibility Chapter 8...