Manual of instructions TT-188
25/37
6.4.
Setting of the temperature
– Heating / Cooling
The required temperature on the temperature controller can be adjusted with the arrow buttons.
The heating mode is indicated by the red diode on the temperature controller. The unit can only heat
when the 0-1 switch (heating) is active.
The cooling mode is indicated by the green diode on the temperature controller.
6.5.
Adjustment of electronic flow control
The electronic flow control measures the actual flow in the medium circuit and displays this value
digitally on the controller.
Following unit of flow can be selected: litres per minute, English (imperial) gallons or American (US)
gallons. When putting the temperature control unit into service the controller shows the unit of flow on
the display for a short moment.
For controlling the minimal flow you can choose between
automatic
and
manual
mode. Standard
programmed is automatic mode.
Automatic mode:
In this mode the alarm value of the flow will be determined as follows:
•
20 seconds after having put the unit into operation (and starting the controller) the actual flow will
be measured and stored. Based on this data the alarm value for the minimal flow will be calculated.
E.g. at 10 l/min the alarm value is at approx. 30% (7 litres)
– at 40 l/min at approx. 20 % (32 litres).
•
The control of the flow is now active and is visualized after a few seconds by the green LED in the
flow control button.
•
As soon as the flow has fallen under the alarm value, the alarm is indicated by the red LED in the
flow control button. The alarm will be reset by pressing the flow control button.
•
The actual flow will be measured and stored. Based on this new data the alarm value will be
calculated.
Manual mode:
Using this modus the alarm value of the flow can be adjusted manually.
•
On the controller the program step 3 (MP-
88) the value must be changed to “0”, respectively
program step 400 (MP-988) the value mu
st be changed to “2” (manual).
•
In the program step 4 (MP-888) respectively the program step 410 (MP-988) the required value for
the alarm value of the minimum flow can be adjusted (factory side 8 l/min).
•
The control of the flow only starts, when the flow control button has been pressed and the green
LED is lit.
•
As soon as the flow has fallen under the alarm value, the alarm is indicated by the red LED.
•
Press the flow control button to activate the monitoring. If the cause of the lower deviation is not
followed up, follows the alarm again. Minimum flow is defined in program step 4 (MP-888).
Содержание TT-188
Страница 8: ...Manual of instructions TT 188 8 37 2 Overview temperature control unit 2 1 Front view ...
Страница 13: ...Manual of instructions TT 188 13 37 4 EU Declaration of conformity ...
Страница 33: ...Manual of instructions TT 188 33 37 12 Components and spare parts 12 1 Overview components and spare parts ...
Страница 34: ...Manual of instructions TT 188 34 37 ...
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......