Page 6-2
Document Ref 903647-001 Rev 3
PAS V3 Pump for Fuel Dispensers
Component Technical Manual
6
PROBLEM REPORT FORM FOR THE PAS V3 PUMP
Is s ued by:
R eport date:
S tation nam e:
Meter reading 1:
l
c ity:
Meter reading 2:
l
c ountry:
Ground piping:
P AS V3 no.:
-Length
m
Ins tallation date:
-Height
m
K ind of fuel:
-D iam eter
m
pipeline
Problem description
¾
1. N o fuel flow
a) Is the pum p running?
¾
yes
¾
no
b) Is the pum p unus ually nois y?
¾
yes
¾
no
If the ans wer is y es , go to point 4. If the ans wer is no:
c ) Is there enough fuel in the underground tank?
¾
yes
¾
no
d) Is air c om ing out of the air vent?
¾
yes
¾
no
e) W hat is the outlet pres s ure (m eas ured at the outlet plug)?
m bar
¾
2. R educ ed fuel flow
a) W hat is the outlet pres s ure w hen running in bypas s m ode?
bar
b) W hat is the inlet pres s ure at the filter box?
m bar
c ) Are the follow ing parts in good order: is the filter box c lean, v-belt?
¾
yes
¾
no
¾
3. P uls ating flow
a) Is the outlet pres s ure c ons tant?
¾
yes
¾
no
b) Is air c om ing out of the air vent?
¾
yes
¾
no
¾
4. E x c es s iv e nois e
a) Is the nois e c om ing from ins ide the pum p?
¾
yes
¾
no
b) W hat is the outlet pres s ure in bypas s m ode?
bar
c ) W hat is the inlet pres s ure at the filter box?
m bar
d) Is it c avitation nois e?
¾
yes
¾
no
Cause of the Problem
Actions done to solve the problem
(list part numbers of new parts used)
Further actions required
Remarks about special environmental or other circumstances
no
More pum ps on one
D is pens er type:
¾
yes
¾
Issue B