![Toho Electronics TTX-800 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/toho-electronics/ttx-800/ttx-800_operation-manual_1124823026.webp)
- 26 -
6.1.10
Communication Monitor Register
・
The communication monitor register is capable of continuous reading.
・
Specify the number of registers you wish to read continuously to the
“
Number of Registers
”
of the read request message.
Upon such, make sure that the specified value is within the register address shown on the table below.
modbus
Name
Command
Remark
Absolute
(DEC)
Relative
(HEX)
40001
0000
Measuring Value
R
Over Scale: 0x7FFF
Under Scale: 0x8000
40003
0002
Manipulated
SV
R
40005
0004
Manipulated Variable of Main
Control
R
40007
0006
Manipulated
Variable
of
Subcontrol
R
40009
0008
Operation State
R
0:READY
1:RUN
2:MANUAL
40011
000A
DO Monitor
R
Returns the state of DO with the bit information.
OFF:0
ON:1
0000 0000 0000 0000
|||| |||| |||| |||+-
OUT1
※
|||| |||| |||| ||+--
OUT2
|||| |||| |||| |+---
OUT3
++++ ++++ ++++ +----
Fixed to 0
※
OUT1 Fixed to 0 if the model is AO
40013
000C
AO Monitor
R
OUT1 DO Model…Fixed to 0.0%
OUT1 AO Model
…
-10.0
~
110.0%
40015
000E
DI Model
R
Returns the state of DI
Nonactive: 0 Active: 1
40017
0010
Information
R
Returns the state with the bit information.
Normal State: 0 Condition has Occurred:1
0000 0000 0000 0000
|||| |||| |||| |||+-
Err0 has occurred
|||| |||| |||| ||+--
Err1 has occurred
|||| |||| |||| |+---
Err2 has occurred
|||| |||| |||| +----
Loop abnormality
has occurred
|||| |||| |||+------
Sensor abnormality
has occurred
|||| |||| ||+-------
OUT1 EV1 has occurred
|||| |||| |+--------
OUT2 EV1 has occurred
|||| |||| +---------
OUT3 EV1 has occurred
|||| |||+-----------
Interlocked
|||| ||+------------
Auto tuning
++++----------------
Fixed to 0
40019
0012
Monitoring of the Remaining
Time of the Timer
R
00:00
…
0x0000
99:59…0x26E7