60
[FV-200CA-AS]
Duty
Amp 1
Duty
Amp 2
Duty
Amp 3
Duty
Amp 4
Duty
Amp 5
Duty
Amp 6
Higher Priority
FV-200CA-AS can handle changeover six duty amplifier with one standby amplifier, if standby amplifier replac-
ing one fault duty amplifier then another duty amplifier with higher priority fault the standby amplifier will
replace the higher fault duty amplifier instead.
Sample case
Duty
Amp 1
Duty
Amp 2
Duty
Amp 3
Changeover
by standby
amplifier
Fault
Normal
Normal
Duty
Amp 1
Duty
Amp 2
Duty
Amp 3
Changeover
by standby
amplifier
Fault
Normal
Fault
Duty
Amp 1
Duty
Amp 2
Duty
Amp 3
Changeover
by standby
amplifier
Fault
Fault
Normal
Duty
Amp 1
Fault
Duty
Amp 3
Fault
BUZZER CTRL
ON
OFF
FAULT
CHANGEOVER
AMP 1
AMP 2
AMP 3
AMP 4
AMP 5
AMP 6
STANDBY
CHANGEOVER AMPLIFIER PANEL FV-200CA-AS
POWER
FV-200CA-AS have 7 LED fault indicator for connected amplifier including standby amplifier fault and have 6
LED changeover indicator. Only one LED changeover indicator can light at once, but LED fault indicator will
light as many as fault occur at duty or standby amplifier.