7.3. FV-200EV-AS Connection
Connecting the FV-200EV-AS enables automatic evacuation guidance broadcasts that are interlocked with
signal from the connected automatic fire alarm system or manually operated voice guidance broadcasts. The
FV-200EV-AS's built-in voice alarm provides pre-recorded fire alert, evacuation, false and clear
announcements.
24V, 250mA
FA INPUT
CONTROL OUTPUT
USB
EV OUTPUT
MICROPHONE
GROUND
VOL
DC IN
FV-200EV-AS
EMERGENCY MESSAGE PANEL
TOA Corporation ,
JAPAN
MADE IN INDONESIA
GROUND
FV-200PP-AS
PRE-AMPLIFIER MIXER PANEL
TOA Corporation ,
JAPAN
MADE IN INDONESIA
24V, 110mA
FV-200EV-AS
FV-200PP-AS
7.4. Timer-Operated Equipment
To make timer-operated broadcasts, connect the device equipped with the play make output to the
FV-200PP-AS's Timer Input as follows. While the Timer Input's (+) and (–) terminals are closed, audio signals
entering the Timer Input are output to all speaker lines.
[Connection Diagram]
[Connection Diagram]
GROUND
FV-200PP-AS
PRE-AMPLIFIER MIXER PANEL
TOA Corporation ,
JAPAN
MADE IN INDONESIA
24V, 110mA
FV-200PP-AS
Timer unit
&
BGM Player
+
-
C
E
H
Play make output
Audio output
31