BASIC PARAMETERS MENU
To change parameters, press and hold the
MENU
button for two (2) seconds. To go into the next
indicator (parameter), press the
MENU
button again until you find the desired parameter.
To change parameter value, use the
or
button.
- the indicator
is pulsating
– setting of desirable temperature of the heat storage tank (30 ÷ 80°C)
- the indicator
is pulsating
– activation/setting of the
STORAGE TANK PROTECTION
function:
00
– protection inactive
10 ÷ 20 – protection active (10 ÷ 20°C)
- the indicator
is pulsating
– setting of the difference in temperatures between the collector and
storage tank at which the pump is switched on
(0 ÷ 30°C)
- the indicator
is pulsating
– setting of the difference in temperatures between the collector and
storage tank at which the pump is switched off
(0 ÷ 20°C)
- the indicator
is pulsating
– setting of the minimum pump output (20 ÷ 100%)
Changes are saved and the
MENU
is closed when:
- no button is pressed for 10 seconds
- the
MENU
button is pressed while the bottom indicator
is displayed.
COLLECTOR PROTECTION
– ON/OFF
To switch on or off the function of
STORAGE TANK PROTECTION
from overheating, disconnect the
controller from the mains supply
, press the
START (+)
button and, without releasing it, switch on
the controller. The screen displays “1” to show that the protection is active or “0” to represent that the
protection is inactive.
To change the setting, use the
START (+)
and
STOP (-)
buttons. To confirm changes and resume
operation, press the
MENU
button.
SAFETY DEVICES
The pump and controller are protected by means of a 500 mA fuse which blows up in emergency
situations (e.g. short-circuit in the pump or controller).
DELIVERY SET
controller
clamps (2 pcs.)
6 mm wall plugs (2 pcs.)