DESCRIPTION OF INDICATOR SYMBOLS 

– 

during controller operation 

 

 

 

- the current heat storage tank temperature is displayed 

 

- the current collector temperature is displayed 

 

- the pump is operating 

 

- the pump is operating regardless of temperature 

 
 

CONTROLLER OPERATION

 

 

The controller makes it possible to switch between two pump operation modes: automatic and 
continuous. The default setting is the automatic mode. The user is able to manually switch on/off the 
continuous mode of pump operation by pressing the 

START 

(

+

) and 

STOP 

(

-

) buttons. 

1. automatic operation mode: 
- the controller activates the pump at full capacity if the collector temperature is higher than the storage 
tank temperature by the preset parameter 

“activation delta” (

). If the difference in temperatures 

decreases, the pump slows down its operation until it stops completely after reaching the preset 
parameter 

“inactivation delta” (

); 

- the heat storage tank is heated until it reaches the temperature set by the user; 

- when the pump is activated, the indicator light 

 is lit. 

2. continuous operation mode: 
- the pump operates regardless of the temperature (e.g. to check pump operation); 

- the indicator light 

 is lit.  

 
Note: After controller connection to the mains supply, the pump always operates in the automatic 
mode. 
 
The controller can protect the heat storage tank from overheating 

– 

STORAGE TANK PROTECTION

In this case, the controller activates the pump if the temperature of the heat storage tank exceeds the 
preset temperature by the value of the 

STORAGE TANK PROTECTION

 parameter and the collector 

is at least 

10°C cooler than the storage tank. 

 
The controller can activate the pump in the emergency procedur

e if the collector’s temperature 

exceeds 99°C despite the preset temperature of the heat storage tank being exceeded – 

STORAGE 

TANK PROTECTION

 from overheating.   

 
 
 

CHANGE OF DISPLAYED TEMPERATURE 

 

 

The controller makes it possible to monitor temperatures measured by both sensors. Switching between 

displayed temperatures can be performed by pressing the 

MENU

 button. The 

 and 

 indicators 

show which of the temperatures is currently displayed.

 

 
 
 
 
 
 
 
 
 
 
 