 S

 

BOILER AUTOMATIC MODE (BLOWER AND STOKER)

4

Use 

MANUAL MODE OF THE STOKER AND BLOWER

 to fire up the boiler (page 3). When coal in the retort has been 

ignited switch to automatic mode by pressing [EXIT]

,

 then pressing [MODE], and then within five seconds 

[]START

. The 

controller starts automatic FIRE UP of the boiler - the blower works at its maximal speed setting, while the stoker regularly 
feeds new portions of coal. FIRE UP mode will start only if the temperature at the boiler sensor is lower than the extinguish 
temperature setting (parameter A3)

Over the first 6 hours after the FIRE UP precedure has been started the controller does 

not take into account the minimal temperature at the return to the boiler

 (parameter E3)

.

When  the  boiler  temperature  exceeds  current  extinguish  temperature  setting  (parameter  A3),  the  controller  enters 
HEATING mode. 
If the parameter A

8

 is set to YES (default

: NO

), as the temperature of the boiler approaches the temperature set by the user 

(parameter  A1)  displayed  on  the  MAIN  SCREEN,  the  amount  of  coal  and  air  is  automatically  reduced.  When  the 
temperature selected by the user is achieved, the controller enters into STANDBY mode. In this mode the stoker and blower 
switch on at regular intervals to prevent furnace from extinguishing.
The controller enters HEATING mode again when the temperature drops by the hysteresis value (parameter A2) below 
boiler temperature.

During heating up of the D.H.W. tank automatic reduction of boiler power is not performed.

In HEATING mode, when boiler temperature drops below the current extinguish temperature setting (parameter A3), the 
controller enters EXTINGUISH mode - the blower and stoker are switched off. 
EXTINGUISH will not start unless FIRE UP has been completed (parameter A4 - default setting: 

6

 hour

s

). 

If during FIRE UP boiler temperature does not exceed EXTINGUISH temperature, once FIRE UP time has passed, the 
controller enters into NOT FIRED UP mode.
In all modes of the controller pumps are run depending on selected settings.

OPERATION WITH THE WIRELESS REMOTE CONTROL ROOM PANEL

Operation of the JOKER DS2P

M

-RC controller with the wireless room control panel is described on pages 12 and 13.

SUMMER MODE (parameter 

K

1

 in 

)

When SUMMER mode is selected, 

a

utomatic reduction of boiler power is not performed. The boiler heats up only the 

D.H.W. tank. SUMMER mode is indicated on the MAIN SCREEN by the

      and 

 

     

icon

s

.

Over the first 6 hours from switching from the SUMMER mode to the WINTER mode the controller does not take into 
account the minimal temperature at the return to the boiler

 (parameter E3)

.

ALERTS

The controller features several boiler alerts: regulated alerts for low or high boiler temperature (parameters A5 and A6) and 
permanent (not regulated) alerts: low temperature at 8°C and high temperature at 92°C. The 92°C alert stops the blower 
and the stoker and fully opens the mixing valve. Even when boiler temperature drops, the "92°C alert" remains active until 
[START] button is pressed.

 

Once the temperature exceeds the alert threshold set by the user, both an audible and visual 

(red diode) alerts are triggered. When boiler reaches the permanent alert temperature only a visual alert is activated.

When temperature of the stoker exceeds the alert temperature setting (parameter C6), the stoker is activated in order to 
shove burning coal from the stoker into the boiler (preventing fire from moving into the coal container). A special screen 
appears to display temperature and duration of coal shoving (parameter C7). Audible and visual (red diode) alerts are 
activated and the mixing valve is fully opened.
Pressing [STOP] on the screen "Shoving fire from the stoker into the boiler' stops the shoving off procedure regardless of 
the temperature of the stoker. When shoving off is discontinued, "STOKER FIRE" symbol appears on the main screen. 
CAUTION: Shoving off of coal from the stoker into the boiler is activated only once in a given working cycle of the controller. 
In order to activate the stoker alert again press [START] - then the "STOKER FIRE" message will disappear from the 
screen.
The 92°C alert has a priority over stoker alert.

The emergency cooling of the boiler in the SUMMER mode (parameter A7) will activate the CH pump and the 

, i

CAUTION: During the 

 there is a risk of increased domestic hot water temperature 

above user settings. The careful use of hot water is recommended.

CAUTION: 

CAUTION: 

DHW tank 

feeding pump

An audible alert and a visual alert (red diode) are activated. 

emergency cooling of the boiler

If the temperature at the return to the boiler falls below the setting of the parameter E3, the controller 

will increase boiler temperature to 65°C.

While the D.H.W. tank is heated up, the controller raises the boiler temperature by 5°C above the current 

temperature setting for the D.H.W. tank (

F

1).

When the blower

 and stoker

 need to be stopped press [MODE], and then within five seconds press [STOP]. Pressing 

[START] restarts the blower

 and the stoker

.

Controller settings

n such a case the valve is fully opened

Содержание JOKER DS2PM-RC

Страница 1: ...ed spaces is maintained at desired levels while the boiler operates in optimal conditions ensuring increased life expectancy The user can limit the number of controlled appliances thanks to flexible c...

Страница 2: ...power supply Otherwise the pump may become damaged General technical data Supply voltage 230V 50Hz Maximum pump output 3x100VA 1x250VA stoker 1x5VA valve Anti stop function pump protection against jam...

Страница 3: ...IN SCREEN START STOP manual mode current temperature of the boiler Turn the knob to set blower speed arrows are flashing 1 Installation of the boiler temperature sensor and thermal breaker switch Fix...

Страница 4: ...t 6 hours from switching from the SUMMER mode to the WINTER mode the controller does not take into account the minimal temperature at the return to the boiler parameter E3 ALERTS The controller featur...

Страница 5: ...45 C Boiler extinguish temperature cannot be higher than the difference of parameters A1 minus A2 minus 5 C A4 Fire up duration 10 480 min default 6 hours A5 low boiler temperature alert 0 50 C defau...

Страница 6: ...the knob or using the dynamically appearing buttons Editing is confirmed by pressing the knob or the SAVE button Pressing EXIT will bring back the previous screen without saving any changes LIST OF P...

Страница 7: ...o change parameters of the C H pump List of groups of parameters will appear on the screen Turn the knob right clockwise to select group D C H pump and then to select press the knob or the SELECT butt...

Страница 8: ...ehind valve is programmable different temperatures can be set for every day and hour of the week parameter H1 The central heating timed programme in use is displayed on the MAIN SCREEN between the CH...

Страница 9: ...valve E2a E2b or E2c above the corresponding E1a E1b or E1c max temp behind valve results in both settings becoming equal E2a day 1 99 C default 35 C E2b night 1 99 C default 20 C E2c economy 1 99 C d...

Страница 10: ...on if 1 the set temperature of domestic hot water has not been achieved and 2 when the temperature at the C H boiler is higher than that inside of the hot water tank by the parameter F4 protection of...

Страница 11: ...take into account the minimal temperature at the return to the boiler parameter E3 F4 DHW tank protection from cooling down 0 15 C default setting 5 C F5 Minimal temperature of the CH boiler at which...

Страница 12: ...l temperature behind valve is edited H high means that room temperature has not been reached and maximal temperature behind valve is edited Pressing the or button again will further increase or decrea...

Страница 13: ...If NO has been selected oker controller operation with is deactivated LIST OF ROOM PANEL PARAMETERS G1 Room temperatures G2 Precision of room temperature control hysteresis 0 1 0 5 C default setting 0...

Страница 14: ...elected day to another day of the week which you select with the knob Press SELECT or the knob Press EDIT or the knob In this screen turn the knob to select time interval to be edited Press NEXT or th...

Страница 15: ...of coal consumption COAL CONSUMPTION PARAMETER MENU group I COAL CONSUMPTION SETTINGS CAUTION It is advisable to verify the estimation of coal consumption performed by the controller from time to time...

Страница 16: ...zech CAUTION Return to default settings does not concern language K8 Information about the controller model software version 5 1 6 0 read only K9 Contrast of the display 1 31 default setting 12 CAUTIO...

Страница 17: ...r defects which can be attributed to the manufacturer TMK sp j shall repair or replace the faulty controller with a defect free device within 14 working days from the date of returning the controller...

Отзывы: