(4) Exhaust Piping [Se]: 

  Unless problems occur, leave the exhaust pipe connected to the condensate 

receiver as designed. 

  When steam is not used as the motive medium, steam clouds (flash steam) 

may come out from the vent pipe [Sv]. In this case it is possible to disconnect 
the exhaust line from the condensate receiver. 
If the exhaust line has to discharge to atmosphere, a sound level of 
approximately 90 – 100 dB may be emitted from the exhaust pipe discharge 
outlet for two to three seconds. If soundproofing measures are necessary, 
install a silencer. (If the exhaust line is connected to the condensate receiver, 
the sound level will be below 60 dB.)   

(5) Condensate Inlet Piping [Si]: 

  Condensate Inlet Pipe [Si] should be as short and straight as possible so that 

condensate naturally flows down into the 

PowerTrap

  Install a 40-mesh or finer strainer [Ki] on the 

PowerTrap

 condensate inlet pipe. 

The installation should be in a location that allows sufficient space for 
maintenance of the strainer. 

  Install a valve [V] and a bypass valve [Vb] on the condensate inlet pipe. This 

allows operation of the equipment while carrying out maintenance work if the 

PowerTrap

 is

 

malfunctioning or needs maintenance. Use a gate valve for 

valve [V] and a globe valve for the bypass valve [Vb]. 

(6) Condensate Outlet Piping [So], Condensate Recovery Line [Sr]: 

  The flow velocity in the pipe should be considered when determining the pipe 

size. 
Condensate in the 

PowerTrap

 is discharged by the motive medium supply 

pressure. The instantaneous flow through the condensate outlet pipe during the 
discharge operation is between 2 and 40 metric tonnes (530 and 10,600 U.S. 
gal) per hour.   
The instantaneous discharge amount should be considered when determining 
the outlet pipe diameter. For each system package, motive medium supply 
pressure and back pressure instantaneous discharge amount, contact 

. If 

you have the "

PowerTrap

 Design & Data Sheet", installed piping should be the 

size recommended by TLV. 

Содержание PowerTrap GP10-1CJ

Страница 1: ...172 65510MA 05 GP Series System Package 27 December 2016 System Package GP10L 1AJ GP14L 1AJ GP14M 1BJ GP10 1CJ GP10 2FJ Copyright 2016 by TLV CO LTD All rights reserved ...

Страница 2: ...ure to read this manual carefully before use and follow the instructions to be sure of using the product properly This instruction manual only describes contents regarding installation of the system package Detailed instructions for PowerTrap unit s included in this system package are not described Please refer to the instruction manual s for each PowerTrap unit If detailed instructions for specia...

Страница 3: ...o observe these precautions Symbols Indicates a DANGER WARNING or CAUTION item DANGER Indicates an urgent situation which poses a threat of death or serious injury WARNING Indicates that there is a potential threat of death or serious injury CAUTION Indicates that there is a possibility of injury or equipment product damage CAUTION Install properly and DO NOT use this product outside the recommend...

Страница 4: ...rge of fluids Do not use excessive force when connecting threaded pipes to the product Over tightening may cause breakage leading to fluid discharge which may cause burns or other injury Use only under conditions in which no freeze up will occur Freezing may damage the product leading to fluid discharge which may cause burns or other injury Use only under conditions in which no water hammer will o...

Страница 5: ...rTrap is a non electric mechanical pump used to discharge high temperature liquid from vacuum pressure or low pressure areas to high pressure areas or from lower to higher elevations This system package is pre assembled with all the necessary devices and pipes to operate the PowerTrap greatly reducing labor required for installation pipings and maintenance The discharge capacity differs depending ...

Страница 6: ... on the condensate receiver Please check the latest product information for the specifications of each model For the latest product information please contact TLV Model Serial Number 2 For the model name of the PowerTrap unit s refer to the nameplate located on the PowerTrap unit s Please check the latest product information for the specifications of the PowerTrap unit s For the latest product inf...

Страница 7: ...ive Medium Supply Connection Condensate Outlet Condensate Outlet Valve Blow Valve Vent Pipe Connection Exhaust Valve Nameplate Motive Medium Supply Valve PowerTrap Condensate Inlet Check Valve Condensate Outlet Check Valve Motive Medium Strainer Condensate Inlet GP10 2FJ Vent Pipe Connection Condensate Receiver Condensate Inlet Valve Motive Medium Supply Connection Condensate Outlet Condensate Out...

Страница 8: ...w Connection Blow Valve bottom of the condensate receiver GP14M 1BJ Condensate Inlet or Overflow Connection Condensate Receiver Motive Medium Supply Valve Motive Medium Supply Connection Condensate Outlet Condensate Outlet Valve Blow Valve Vent Pipe Connection Exhaust Valve Nameplate PowerTrap Condensate Inlet Check Valve Condensate Outlet Check Valve Motive Medium Strainer Condensate receiver may...

Страница 9: ...tive Medium Supply Line Blow Line Condensate Line Lg Backflow Water Hammer Prevention Check Valve Condensate Recovery Line Sr Temperature Controller Equipment Pressure Steam for Heating Motive Medium Supply Pressure Pm Primary Pressure for Motive Medium Flash Steam Vent Pipe Overflow Pipe Pump Exhaust Back Pressure Steam Trap TLV Power Trap Steam Trap Steam Trap Steam using Equipment Other Steam u...

Страница 10: ...he exhaust pipe Se close to where it connects to the condensate receiver This measure is not necessary when the motive medium is compressed air or nitrogen 3 Pressure Reducing Valve on the Motive Medium Supply Piping Rm When the supply pressure of the motive medium is greater than 1 05 MPaG 150 psig 10 5 barg install a TLV COSPECT Series pressure reducing valve Make sure that the motive medium pre...

Страница 11: ...he PowerTrap condensate inlet pipe The installation should be in a location that allows sufficient space for maintenance of the strainer Install a valve V and a bypass valve Vb on the condensate inlet pipe This allows operation of the equipment while carrying out maintenance work if the PowerTrap is malfunctioning or needs maintenance Use a gate valve for valve V and a globe valve for the bypass v...

Страница 12: ...OoP RaPer may splasO TOere is a possibiliPy of condensed OoP RaPer dripping from venP pipe ouPleP Make sure Po exPend Po ROere people do noP pass FondensaPe Receiver VenP Pipe FlasO SPeam To PoRerTrap FlasO SPeam The flow velocity in the pipe should be considered when determining the pipe size 1 If flash steam can be discharged from overflow pipe Install overflow pipe and vent pipe separately 2 If...

Страница 13: ...a rise in the piping is longer than 30 m 100 ft return water hammer may occur in the piping after a discharge cycle finishes To prevent this installation of a spring return type check valve just above the rise is recommended 9 Check Valve to Prevent Backflow Water Hammer If length B in the following figure is longer than 500 mm 1911 16 in and steam including flash steam enters the condensate recov...

Страница 14: ... is recommended GP10 1CJ Anchor Bolt M16 4 pcs Embedment depth of 150 mm 6 in or more is recommended GP10 2FJ Anchor Bolt M16 4 pcs Embedment depth of 150 mm 6 in or more is recommended Refer to the latest drawings for the anchoring positions of each model For the latest product information please contact TLV Maintenance Space The maintenance space shown in the figure below should be provided to e...

Страница 15: ...ge 27 Dec 2016 14 GP14M 1BJ 400 mm 153 4 in 400 mm 153 4 in 800 mm 301 2 in 800 mm 301 2 in GP10 1CJ 400 mm 153 4 in 800 mm 301 2 in 800 mm 301 2 in 400 mm 153 4 in GP10 2FJ 800 mm 301 2 in 800 mm 301 2 in 800 mm 301 2 in 500 mm 1911 16 in ...

Страница 16: ...of fluids CAUTION Install properly and DO NOT use this product outside the recommended operating pressure temperature and other specification ranges Improper use may result in such hazards as damage to the product or malfunctions which may lead to serious accidents Local regulations may restrict the use of this product to below the conditions quoted CAUTION Be sure to use only the recommended comp...

Страница 17: ...flowing condensate lb h The GP10L GP14L GP14M and GP10 condensate discharge capacity for each discharge operation is listed below The amount of time required for each discharge operation will be between 3 and 30 seconds depending on the back pressure and the motive medium pressure GP10L 1AJ approx 6 liters 1 6 U S gal GP14L 1AJ approx 8 liters 2 1 U S gal GP14M 1AJ approx 12 5 liters 3 3 U S gal G...

Страница 18: ...cle the sound of flow in the exhaust pipe should be heard During the pumping discharge part of the cycle flow in the motive medium supply pipe should be heard c Condensate should not accumulate in the steam using equipment and the temperature of the equipment should not be abnormally low d There should be no condensate overflow from the overflow pipe or vent pipes e There should be no continuous s...

Страница 19: ...e to improper installation use handling etc by other than TLV CO LTD authorized service representatives 2 Malfunctions due to dirt scale rust etc 3 Malfunctions due to improper disassembly and reassembly or inadequate inspection and maintenance by other than TLV CO LTD authorized service representatives 4 Malfunctions due to disasters or forces of nature 5 Accidents or malfunctions due to any othe...

Отзывы: