Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or
malfunctions which may lead to serious accidents. Local regulations
may restrict the use of this product to below the conditions quoted.
CAUTION
Use hoisting equipment for heavy objects (weighing approximately
20 kg (44 lb) or more). Failure to do so may result in back strain or other
injury if the object should fall.
CAUTION
Take measures to prevent people from coming into direct contact with
product outlets. Failure to do so may result in burns or other injury from
the discharge of fluids.
CAUTION
Do not use excessive force when connecting threaded pipes to the
product. Over-tightening may cause breakage leading to fluid
discharge, which may cause burns or other injury.
CAUTION
Installation, inspection, maintenance, repairs, disassembly, adjustment and valve
opening/closing should be carried out only by trained maintenance personnel.
1. Before installation, be sure to remove all protective seals.
2. Before installing the product, open the inlet valve and blow out the piping to
remove any piping scraps, dirt and oil. Close the inlet valve after blowdown.
3. Install a bypass valve and inlet and outlet isolation valves for use in the event of trap
failure or when performing maintenance.
4. Install a strainer (40
– 60 mesh) ahead of the product.
5. Install the product so that the arrow on the body is pointing in the direction of flow.
6. The product should be inclined no more than 5° horizontally and front-to-back. Be
sure to leave adequate clearance for a maintenance space above the trap cover.
7. Connect outlet piping. Be sure to size outlet piping large enough to accommodate
any flash steam that may form to prevent any increase in back pressure and allow
at least 1 m (3.3 ft) straight piping to avoid possible pipe erosion.
8. Open the inlet and outlet valves and ensure that the product functions properly.
If there is a problem, determine the cause
using the “Troubleshooting” section in this
manual.
Tolerance Angle for Installation: 5°
Maintenance Space:
Minimum 300 mm (11
3
/
4
in)
5
°
5
°
5
°