172-65465MA-04 (JH8R-P) 11 May 2018
15
Options
The options shown below are available for this product on
request. Please compare with the product you received.
Options for Area A (standard: with drain plug)
Without Drain Plug
Options for Area B (standard: with cover plug)
A pressure-balancing line connector can be attached to the place where the
standard product has the cover plug.
Socket Type
(Model:JH8R-W)
Flange Type
(Model: JH8R-F)
•
In principle, steam traps automatically discharge inflowing condensate. However, if
low-temperature condensate in the piping blocks the trap inlet passage,
displacement inside the piping of steam by condensate is obstructed and
condensate can no longer flow into the trap (steam-locking). Traps only function in
the presence of condensate inflow. A pressure-balancing line prevents the
occurrence of steam-locking.
Install the pressure-balancing line in the following manner:
Example: Heat Exchanger
Attach the pressure-balancing line
to the trap and to either the
equipment or to an area with a
steam space.
Pressure-balancing Line
Steam