172-65193A-06 (G8) 8 Jul 2015
6
Installation
Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or
malfunctions which may lead to serious accidents. Local regulations
may restrict the use of this product to below the conditions quoted.
CAUTION
Take measures to prevent people from coming into direct contact with
product outlets. Failure to do so may result in burns or other injury from
the discharge of fluids.
CAUTION
Do not use excessive force when connecting threaded pipes to the
product. Over-tightening may cause breakage leading to fluid
discharge, which may cause burns or other injury.
CAUTION
Installation, inspection, maintenance, repairs, disassembly, adjustment and valve
opening/closing should be carried out only by trained maintenance personnel.
1. Before installation, be sure to remove all protective seals.
2. Before installing the product, open the inlet valve and blow out the piping to
remove any piping scraps, dirt and oil. Close the inlet valve after blowdown.
3. Install the product so the arrow on the body is pointing in the direction of flow.
4. The trap should be inclined no more than 5° horizontally and front-to-back.
5. To insure proper condensate flow into the trap, remove the balancing line plug
and install a pressure-balancing line. Connect the end of the pressure-balancing
line to the air main or an area with an air pocket. For more details, see the section
“The Need for a Pressure-balancing Line”.
6. To facilitate inspection and maintenance, install a union or a flange where the
product has connections (inlet, pressure-balancing line, condensate outlet). For
more details, see the section “The Need for a Pressure-balancing Line”.
7. After priming through the pressure-balancing port, open the inlet valve and check
to make sure that the product functions properly.
If there is a problem, determine the cause using the “Troubleshooting” section in this
manual.
Tolerance Angle for Installation - 5°
Make sure the trap is installed with the raised
lettering on the body horizontal.