background image

 

TLT-Turbo GmbH 

Installation, operating and maintenance instructions. 

For axial flow fans 

Page 8 

Series fan division 

Bad Hersfeld

 

Type AXO ... / ... 

 

of 12 

 

MBW-AXO.DOC 

Issue: 03.2004 

 

 

Connection has to be made by an electrician according to VDE regulations. 
Observe the indications on the nameplate! 
Compare mains voltage! 
Connect the motor as shown on the circuit diagram in the conduit box. 
 
If cable entries in the conduit box are not used, they have to be carefully locked to 
prevent dust and moisture from entering the conduit box. Tighten all contact 
screws and nuts properly, to avoid transition resistance. 
 
Screwed cable glands have to be equipped with pull-relief. 
 

• 

For outdoors installation the supply cable has to be inserted waterproof from 
below or the side into the conduit box on the fan. 

 

• 

No local isolator should be mounted on the fan. It should be mounted in the 
power supply cable near the fan. 

 

• 

Standard motors have no motor protection.

 

 

On site the motor has to be protected with an overload current protection.

 

Upon special wish they can be equipped with barretter (thermal resistor 

protection) or thermal contacts. The required tripping units have to be provided 
by the customer.

 

 
11. Trial run / startup 
 

 

 

 

 

 

 

 

BEFORE TRIAL RUN AND STARTUP BY ALL MEANS READ 
THE SECTION "OPERATIONAL SAFETY" AGAIN. 
 
Proceed as follows: 
 

Clean the fan and remove foreign objects (tools, dirt etc.) before startup of the fan. 
 
Check if all screw joints are tight. 
 
For open inlet and outlet a guard must be mounted. Make sure it is. 
 
The connection pieces in the inlet and outlet and the complete channel system 
must be completely mounted.

 

 

After having connected the fan motor you have to check if the motor turns to the 
correct direction: When looking from the motor side the motor has to turn to the 
left. (If you look from the inlet of the impeller, it has to turn to the right). The 
direction of rotation must be the same as indicated by the arrow. 
 
If the direction of rotation is wrong, the poles of the motor have to be changed. 
(change phases in the conduit box or the switch cabinet.) 
Make sure that the impeller does not touch the housing. 

 

Measure the current absorption of the motor and compare it with the max. current 
consumption on the nameplate. 

 

Содержание AXO Series

Страница 1: ...enance instructions For axial flow fans Page 1 Series fan division Bad Hersfeld Type AXO of 12 MBW AXO DOC Issue 03 2004 Installation operation and maintenance instructions for axial flow fans AXO Sta...

Страница 2: ...vice 4 4 Operational safety 4 5 Transport 5 6 Scope of delivery 6 7 Intermediate storage 6 8 Design 6 9 Technical information 6 10 Installation and mounting 7 11 Trial run startup 8 12 Breakdowns 9 13...

Страница 3: ...rights regarding the contents of these IOM s and technical changes for technical improvement of our fans 2 Applications The axial fan is build according to the state of the art and it is failsafe The...

Страница 4: ...y observed The user has to make sure that only qualified staff work with the fan Necessary works may only be carried out by properly trained staff with sufficient experience and knowledge of the relev...

Страница 5: ...ices may only be removed if the fan is out of action For all types of work on the fan as a rule it has to be out of action The impeller has to be locked to prevent turning After repair works you have...

Страница 6: ...on air direction D or S Conduit box mounted at the outer wall of the fan housing or on the motor accessible via inspection door The impeller is mounted on the motor shaft end It is not adjustable Fan...

Страница 7: ...flexible connections Mount flexible connection exactly not staggered Observe length of installation exactly If the fans are installed on vibration dampers an extension duct is required For installati...

Страница 8: ...ection Upon special wish they can be equipped with barretter thermal resistor protection or thermal contacts The required tripping units have to be provided by the customer 11 Trial run startup BEFORE...

Страница 9: ...ressure increase and compare the values with the nameplate 12 Breakdowns If after some time the fan starts vibrating the cause may be the following a Particles sticking on the impeller blades Troubles...

Страница 10: ...spection book 14 Description of the impeller Impeller hub of aluminum blades of plastic Depending on the desired output they are supplied with 6 8 9 10 or 12 blades The impeller blades are not adjusta...

Страница 11: ...disassembled At the same time the winding and other parts should be cleaned The bearings have to be thoroughly cleaned with benzine After evaporation of the detergent first class grease has to be fil...

Страница 12: ...act our field staff or the specialists in our Bad Hersfeld plant 17 Annex Assembly of the impeller Slightly grease the end of the shaft Then mount the wheel using a special fitting too Threaded hole i...

Отзывы: