TLT-Turbo GmbH
Installation, operating and maintenance instructions.
For axial flow fans
Page 6
Series fan division
Bad Hersfeld
Type AXO ... / ...
of 12
MBW-AXO.DOC
Issue: 03.2004
6. Scope of delivery
Upon receipt of the shipment check the packing lists to make sure the shipment is
complete. If you are missing parts please report in writing to the shipping
department of TLT-Turbo GmbH, Bad Hersfeld.
7. Intermediate storage
If the fan is not installed immediately after shipment, it has to be properly stored at
a protected location. The fan has to be properly covered to make sure no dust or
moisture can enter the fan.
Turn the impeller by hand several rotations once a month.
8. Design
Directly driven axial fan without outlet guide vane.
Motor in air stream (without encapsulation), air direction "D" or "S".
Conduit box mounted at the outer wall of the fan housing, or on the motor
(accessible via inspection door).
The impeller is mounted on the motor shaft end. It is not adjustable.
Fan housing with drilled flanges DIN 24154 - series 3.
Max. working temperature with motor
iso-cl.
B
40° C
F
60°
C
Motors mounted on the foot.
9. Technical information
Air inlet and outlet
The characteristic curves imply a uniform irrotational speed distribution in the fan
inlet. This means for instance that an inlet nozzle has to be mounted in an open
inlet.
If mounted in channels or pipelines an inlet or discharge area of 1.5 times the
diameter of the fan has to be provided.
If the design does not allow that, baffle plates have to be mounted to optimize the
air flow, so that the air speed is as equal as possible when entering the fan.
For an open outlet of the fan the shock loss in relation to the discharge speed (ring
surface) has to be observed.
Motor power calculation