Creation: 1.31 – 2014
2-7-13
GPU - 406
GPU - 409
90KVA ACOP Limit
– Set to Off or On, on GPU with 2 AC Outputs, Limit the overload to 90KVA when
only one OP is switched ON. Default = On.
DC Microswitch Enable
– Set to Off or On, on GPU with 28.5VDC TR option, if optional DC Cable
Micro-switch is fitted change this to ON. Function is to switch OFF the DC Output if the DC Cable is un-
plugged from the aircraft. Uses Pin 35 Input to GCM2. Default = Off (not fitted).
Remote Control Enable
– Set to Off or On. On Tug-Mounted GPU, a Remote Control Panel is fitted in
the drivers cab with two illuminated push switches to control the Engine Start/Stop and AC400Hz
Off/On. The switches connect to Pins 35 and 36 Inputs to GCM2 respectively. The Engine Run Beacon
output drives the engine start indicator light and flashes to indicate starting or stopping, when this
option is used. Default = Off (no remote panel fitted).
Ground Power Unit characteristics
These parameters are normally configured using the “Load Defaults” function as described
above, they may be viewed or adjusted individually if required, but they do not normally
require adjustment unless specified.
Note, Some parameters affecting AC Voltage regulation are set differently for Build A and later
Build B hardware GCM2 with serial numbers of 600 or higher. The firmware will detect which
hardware build is used and set the defaults automatically when “Load Defaults” is used.
KVA Machine
– Set this number to the proper KVA rating (i.e. 90 for 90KVA units). This setting
affects the allowed overload output, and the model designation that appears at the top left of the
main operation screen. It also affects the output current sensing scaling.
Default = 120kVA but will be set by the Load Defaults and not need further adjustment.
Ena AC Output
– Change this to the available number of 400 Hz AC outputs (00, 01, or 02).
Default = 02
Ena DC Output
– Change this to the available number of 28.5VDC outputs (00 or 01). Default = 00
Idle RPM
– Change this to the appropriate engine idle RPM. Default = 1000
Note- The Idle RPM adjustment has no effect on machines fitted with Tier4f exhaust after
treatments
Property of American Airlines
Содержание GPU-406
Страница 4: ...P r o p e r t y o f A m e r i c a n A i r l i n e s...
Страница 18: ...P r o p e r t y o f A m e r i c a n A i r l i n e s...
Страница 22: ...P r o p e r t y o f A m e r i c a n A i r l i n e s...
Страница 48: ...P r o p e r t y o f A m e r i c a n A i r l i n e s...
Страница 54: ...P r o p e r t y o f A m e r i c a n A i r l i n e s...