4.2.4 Inhibit time of EMCY (0x1015)
Table 16: 0x1015 object description
Attribute
Value
Index
0x1015
Name
Inhibit time EMCY
Object code
Variable
Data type
U16
Category
Optional
Table 17: 0x1015 entry description
Attribute
Value
Sub-index
0x00
Access
RW
PDO mapping
No
Value range
U16 (multiple of 100
s)
Default value
0x0000
Inhibit time is a minimum time between two consecutive emergency objects produced by node.
4.2.5 Producer heartbeat time (0x1017)
Table 18: 0x1017 object description
Attribute
Value
Index
0x1017
Name
Producer heartbeat time
Object code
Variable
Data type
U16
Category
Mandatory
Table 19: 0x1017 entry description
Attribute
Value
Sub-index
0x00
Access
RW
PDO mapping
No
Value range
U16 (multiple of 1ms)
Default value
0x03E8 (1000ms)
The value for heartbeat time is given in multiples of 1ms. The value 0 disables the producer
heartbeat. Dynamic heartbeat time is affected instantly. But in order to keep configuration after
reboot a save is needed. Node-ID is affected after reboot.