If you have any questions about your IN-FORCER or if it requires adjustment, repair or routine maintenance, we suggest that
you contact your installer, contractor or service agency. 

2.

If you require technical information contact Tjernlund Products, Inc. at 1-800-255-4208.

When contacting Tjernlund Products, Inc., please have the following information available:

1.

Model number and date code of the IN-FORCER 

2.

Name and address of installer and service agency

3.

Date of original installation and dates any service work was performed

4.

Details of the problem

LIMITED PARTS WARRANTY AND CLAIM PROCEDURE

Tjernlund Products, Inc. warrants the components of the IN-FORCER for one year from date of installation.  This warranty covers
defects in material and workmanship.  This warranty does not cover normal maintenance, transportation or installation charges  for
replacement parts or any other service calls or repairs.  This warranty DOES NOT cover the complete IN-FORCER if it is operative,
except for the defective part.

Tjernlund Products, Inc. will issue credit or provide a free part to replace one that becomes defective during the one year warranty peri-
od.  If the part is over 18 months old, proof of date of the installation in the form of the contractor sales / installation receipt is necessary
to prove the unit has been in service for under one year.  All receipts should include the date code of the IN-FORCER to ensure that the
defective component corresponds with the complete unit.  This will help preclude possible credit refusal.

115V not present

No

No

SYMPTOM 3: IN-FORCER PAI-G (GAS) SERIES WILL NOT RUN ON CALL FOR HEAT

Step 2.
With thermostat calling for heat, measure for 24
volts across the ORANGE and BLUE terminals on
IN-FORCER relay.
Result: Measure 24V.

Step 1.
Confirm that all 115 volt circuits are complete to
the IN-FORCER.  Check the electrical plug to wall
receptacle, fuses and circuit breakers.

Step 5.
Repeat step 1-4 or contact Tjernlund Products for
further assistance.

115V is present

Yes

Yes 

Yes 

Solution: Reestablish 115 volts to IN-FORCER.

No 

Solution: Contact 
appliance / thermostat 
manufacturer for further
assistance.

Note: For further assistance contact Tjernlund Products, Inc.
Technical Customer Service Department at 1-800-255-4208.

Step 3.
With 24 volts present across the ORANGE and BLUE
leads of relay, check for voltage across the YELLOW of
Fan Proving Switch and ORANGE of relay.
Result: Measure 24V.

Step 4.
Caution: Disconnect the 115 volt power supply to the IN-
FORCER before attempting the following procedure.
a) Remove the two BLACK leads from contact side of
relay and connect them together.
b) Reestablish the 115 volt power source to IN-FORCER.
Result: IN-FORCER should run constantly.

Step 2.1
Measure voltage on
thermostat or aquastat
when calling for heat.
Result: Measure 24 V.

Yes

Solution: Replace IN-FORCER relay.
Part # 950-1040

No 

Solution: Replace IN-FORCER motor.
Part # 950-3022.

Содержание IN-FORCER PAI-10

Страница 1: ...Inc All rights reserved P N 8504038 THIS DEVICE MUST BE INSTALLED BY A QUALIFIED PERSON READ INSTRUCTIONS CAREFULLY PRIOR TO INSTALLATION AND OPERATION OF THE AIR INTAKE SYSTEM REV A 5 01 TJERNLUND PR...

Страница 2: ...C Hole Template 18 IN FORCERTM is a trademark of Tjernlund Products Inc for IN FORCER air intakes DESCRIPTION The IN FORCER combustion fans are mechanical air intake fans designed and Listed for use w...

Страница 3: ...t additional combustion air will eliminate carbon monoxide spillage into the home SAFETY INSPECTION OF A PREVIOUSLY USED OIL APPLIANCE Perform prior to IN FORCER installation The following procedure i...

Страница 4: ...ts from the National Fuel Gas Code ANSI Z223 1 NFPA 54 Appendix H IN FORCER TERMINOLOGY INTAKE ELBOW TERMINATION CLEARANCES The IN FORCER has been Listed in accordance with the 1990 BOCA national Mech...

Страница 5: ...diameter PVC pipe lengths from 2 to 20 feet The left hand column has outlet 6 diameter pipe lengths from 0 to 20 feet Pipe lengths must be calculated in equivalent feet See Diagram H Page 6 With corr...

Страница 6: ...ding etc following the template outline for the pipe See Diagram D 5 Knock out material exposing hole through the wall TRUSS MOUNTING If IN FORCER will be mounted on a floor truss instead of a joist f...

Страница 7: ...traight pipe Each 90 degree elbow of 6 metal vent pipe is equal to 10 feet of straight pipe each 45 degree elbow is equal to 5 feet of straight pipe For an example of how to calculate equivalent feet...

Страница 8: ...quivalent lengths must be calculated See Diagram H Page 6 The discharge should terminate three feet from a barometric draft control or air intake of an appliance If this is not possible terminate on s...

Страница 9: ...hat the electrical interlock of the IN FORCER is always done at the final signal which would normally start the burner motor All thermostats zones limits and circula tors are to be wired as normally d...

Страница 10: ...trols as nor mally done when conventional venting before continuing Disconnect power from the appliance before attempting to interlock IN FORCER The instructions below assume that the IN FORCER and SS...

Страница 11: ...FORCER INTERLOCKED ON 24V GAS APPLIANCES As the thermostat aquastat senses a call for heat the internal switch of the the thermostat aquastat will close The switch closure sends current through the in...

Страница 12: ...rlock IN FORCER Step 1 Cut wire that is factory installed to the TH or MV HOT terminal of gas valve Step 2 Connect YELLOW wire from IN FORCER control cable to TH or MV HOT of gas valve Step 3 Connect...

Страница 13: ...assume that the IN FORCER and Power Venter are installed at the same time Step 1 Remove wire connected to the MV HOT terminal on appliance electronic ignition module Step 2 Reconnect wire removed in s...

Страница 14: ...steps 3 6 3 Close all doors and windows of the building If heating equipment is installed in a utility room or closet close the entrance door to the room Close fireplace dampers 4 Turn on all equipme...

Страница 15: ...Products Inc Technical Customer Service Department at 1 800 255 4208 Wiring not correct No No SYMPTOM 1 IN FORCER PAI O OIL SERIES RUNS BUT BURNER DOES NOT FIRE SYMPTOM 2 IN FORCER PAI O OIL SERIES W...

Страница 16: ...ppliance calling for heat and the IN FORCER running check for voltage across YELLOW and RED control cable leads Result Measure 24 volts Step 1 Recheck all wiring per the installation instructions Step...

Страница 17: ...r under one year All receipts should include the date code of the IN FORCER to ensure that the defective component corresponds with the complete unit This will help preclude possible credit refusal 11...

Страница 18: ...ser of this product that the product will be free from defects due to faulty material or workmanship for a period of 1 year from the date of orig inal purchase or delivery to the original purchaser wh...

Страница 19: ...18...

Отзывы: