Step 1: Remove wire connected to the TH(HOT) terminal on appliance gas valve.
Step 2:  Reconnect wire removed in step 1 to the two BLUE wires in Power Venter.
Step 3:  Connect the ORANGE wire from Power Venter electrical box and the RED form the IN-FORCER 

control cable to the TR(COM) terminal on appliance gas valve.

Important:

DO NOT remove the factory pre-wired connection on this terminal.

Step 4: Connect the YELLOW wire in Power Venter electrical box to the BLUE wire from IN-FORCER control cable.
Step 5: Connect the YELLOW wire from IN-FORCER control cable to the TH(HOT) terminal on appliance gas valve.

WIRING MODELS PAI-1G & PAI-2G WITH SINGLE ZONE GAS OR OIL FURNACE TERMINAL STRIP/FAN CENTER

Step 1: Remove T-Stat wire connected to W on furnace terminal strip/fan center and connect it to BLUE 

wire of IN-FORCER control cable.

Step 2: Connect YELLOW wire from IN-FORCER control cable to W on furnace terminal strip/fan center
Step 3: Connect RED from IN-FORCER control cable to C/Common on furnace terminal strip/fan center.

SYSTEM OPERATION CHECK-0UT

1.

Adjust thermostat or appliance to call for heat.

2.

Verify that IN-FORCER operates first, prior to burner ignition.
Allow heating equipment and IN-FORCER to operate continuously while performing steps 3-6.

3.

Close all doors and windows of the building.  If heating equipment is installed in a utility room or closet, close the entrance 
door to the room.  Close fireplace dampers.

4.

Turn on all equipment in the structure that exhausts indoor air during the operation, i.e. turn on clothes dryer, exhaust fans, 
such as range hood, bathroom and exhaust whole house fans.

5.

Allow IN-FORCER and equipment to operate for at least five minutes.

6.

Place a smoke source a couple of inches from draft hood or draft diverter and verify that appliance is pulling in smoke, (See 
Diagram N). 

If appliance is venting properly, smoke source will be pulled in.  If smoke is not pulled in, a blocked flue or negative house pressure
exists.  Call a heating professional to examine the problem.

MAINTENANCE

The IN-FORCER must be inspected every 3 to 6 months.  Points of inspection are:

1. 

Motor:

Motor must rotate freely.  The fan motor is permanently sealed and requires no oiling.

2.  

Wheel:

Wheel must be clean of any foreign substance like leaves, lint or other items.  Remove all foreign material from 

blower assembly before operation.

3.  

Intake Elbow: 

Intake elbow screen should be clear of any foreign substance like leaves, lint or other items.  Check screen 

every 3 to 6 months for foreign material.  Remove all foreign material from intake system before operation.

The IN-FORCER now features easy pull down servicing for maintenance, see isometric diagram on bottom of page 17.

DIAGRAM N

Содержание IN-FORCER PAI-10

Страница 1: ...Inc All rights reserved P N 8504038 THIS DEVICE MUST BE INSTALLED BY A QUALIFIED PERSON READ INSTRUCTIONS CAREFULLY PRIOR TO INSTALLATION AND OPERATION OF THE AIR INTAKE SYSTEM REV A 5 01 TJERNLUND PR...

Страница 2: ...C Hole Template 18 IN FORCERTM is a trademark of Tjernlund Products Inc for IN FORCER air intakes DESCRIPTION The IN FORCER combustion fans are mechanical air intake fans designed and Listed for use w...

Страница 3: ...t additional combustion air will eliminate carbon monoxide spillage into the home SAFETY INSPECTION OF A PREVIOUSLY USED OIL APPLIANCE Perform prior to IN FORCER installation The following procedure i...

Страница 4: ...ts from the National Fuel Gas Code ANSI Z223 1 NFPA 54 Appendix H IN FORCER TERMINOLOGY INTAKE ELBOW TERMINATION CLEARANCES The IN FORCER has been Listed in accordance with the 1990 BOCA national Mech...

Страница 5: ...diameter PVC pipe lengths from 2 to 20 feet The left hand column has outlet 6 diameter pipe lengths from 0 to 20 feet Pipe lengths must be calculated in equivalent feet See Diagram H Page 6 With corr...

Страница 6: ...ding etc following the template outline for the pipe See Diagram D 5 Knock out material exposing hole through the wall TRUSS MOUNTING If IN FORCER will be mounted on a floor truss instead of a joist f...

Страница 7: ...traight pipe Each 90 degree elbow of 6 metal vent pipe is equal to 10 feet of straight pipe each 45 degree elbow is equal to 5 feet of straight pipe For an example of how to calculate equivalent feet...

Страница 8: ...quivalent lengths must be calculated See Diagram H Page 6 The discharge should terminate three feet from a barometric draft control or air intake of an appliance If this is not possible terminate on s...

Страница 9: ...hat the electrical interlock of the IN FORCER is always done at the final signal which would normally start the burner motor All thermostats zones limits and circula tors are to be wired as normally d...

Страница 10: ...trols as nor mally done when conventional venting before continuing Disconnect power from the appliance before attempting to interlock IN FORCER The instructions below assume that the IN FORCER and SS...

Страница 11: ...FORCER INTERLOCKED ON 24V GAS APPLIANCES As the thermostat aquastat senses a call for heat the internal switch of the the thermostat aquastat will close The switch closure sends current through the in...

Страница 12: ...rlock IN FORCER Step 1 Cut wire that is factory installed to the TH or MV HOT terminal of gas valve Step 2 Connect YELLOW wire from IN FORCER control cable to TH or MV HOT of gas valve Step 3 Connect...

Страница 13: ...assume that the IN FORCER and Power Venter are installed at the same time Step 1 Remove wire connected to the MV HOT terminal on appliance electronic ignition module Step 2 Reconnect wire removed in s...

Страница 14: ...steps 3 6 3 Close all doors and windows of the building If heating equipment is installed in a utility room or closet close the entrance door to the room Close fireplace dampers 4 Turn on all equipme...

Страница 15: ...Products Inc Technical Customer Service Department at 1 800 255 4208 Wiring not correct No No SYMPTOM 1 IN FORCER PAI O OIL SERIES RUNS BUT BURNER DOES NOT FIRE SYMPTOM 2 IN FORCER PAI O OIL SERIES W...

Страница 16: ...ppliance calling for heat and the IN FORCER running check for voltage across YELLOW and RED control cable leads Result Measure 24 volts Step 1 Recheck all wiring per the installation instructions Step...

Страница 17: ...r under one year All receipts should include the date code of the IN FORCER to ensure that the defective component corresponds with the complete unit This will help preclude possible credit refusal 11...

Страница 18: ...ser of this product that the product will be free from defects due to faulty material or workmanship for a period of 1 year from the date of orig inal purchase or delivery to the original purchaser wh...

Страница 19: ...18...

Отзывы: