background image

17

To save the changes, press the MODE/SAVE button until the display reverts to the information that was 
displayed before you began changing the settings.

Figures in the display are blinking.

Display shows “– –,” if Timken C-Power was previously off.
Display shows “. % Vol.,” if Timken C-Power was previously 

Figure 18

switched on.

To check the changes, press the MODE/SAVE button again, until the display switches to the 
configuration mode and shows the current settings.

If You Do Not Want to Save the Changes

If you do 

not 

want to save the changes that you have made in the configuration menu, press the

ON/OFF/SELECT button until the display shows the symbol “– –“ for OFF or the remaining volume of the 
C-Power LV unit in % VOL. The original settings remain valid.

Automatic Termination of the Configuration Mode

In the configuration mode, if you do not press a button for ten seconds, the control system automatically 
switches back to the previously set mode (“ON“ or “OFF“) without saving the changes. The original 
settings remain valid.

Additional Discharge

With an additional discharge, a lubrication point can be supplied with an additional amount of the 
lubricant. For an additional discharge, the lubrication system must be switched on (the display will 
show the remaining volume). Press both buttons simultaneously and hold them down (refer to figure 19).

Figure 19 

For an additional discharge, press both buttons at the same time and hold them down.

An additional discharge is only possible at temperatures above 32° F (0° C) (figure 20 – ice crystal is not 
visible). Each additional discharge reduces the remaining discharge period, as an increased amount of 
the lubricant has been supplied. This must be factored into the lubrication and maintenance schedule. A 
calculation is possible using the formula from chapter 6.9 and the remaining volume displayed.

The minimum period between two additional discharges is 30 seconds. If you continue to press the 
buttons during that period, further additional discharges will follow. 

MODE

SAVE

MODE

SAVE

ON/OFF

SELECT

Config.
Time

Days

24

– –

Содержание C-POWER 250

Страница 1: ...Timken C Power Lubricator Operating System Manual...

Страница 2: ......

Страница 3: ...12 5 1 Display Elements 5 2 Function Indication on the Display 5 3 Function Indication via the LED Signal Lights 5 4 Control Buttons 6 Operation and Control 13 6 1 Preparations 6 2 Questions to Ask Pr...

Страница 4: ...me and improve safety 1 1 Delivery Content Timken C Power will be delivered according to customer specifications for type of grease and size of the C Power LV unit The user will only need to assemble...

Страница 5: ...ing addition and or variation is considered inappropriate 1 5 Legal Requirements Liability The information data and tips contained in this operating manual were current as of the printing date No clai...

Страница 6: ...efore any changes are made Only original tube connections and connectors from Timken can be used on or with the lubrication system These will withstand high pressure up to 360 psi 25 bar Ambient media...

Страница 7: ...rease Correct Answer 3 m maximum tube length for standard grease 5 m maximum tube length for low temperature grease arrow 1 meets the dashed line of the standard grease range at 3 m 2 You want to use...

Страница 8: ...ower LV unit which can be supplied in 250 cc and 500 cc versions Lubricant can be requested by the customer Use only Timken C Power LV units Battery set consisting of two batteries The batteries are n...

Страница 9: ...t the lubrication points and the complete lubricant tube are pre lubricated with the same lubricant that is contained in the C Power LV unit To do this Timken offers a 400 g lubrication cartridge for...

Страница 10: ...position of the jumper It must correspond to the size of the C Power LV unit refer to figure 4 and chapter 7 1 Figure 4 b Place the C Power LV unit inside the protection cover and remove the plug refe...

Страница 11: ...r to figure 6 Figure 6 d Place the C Power LV unit with its protection cover on the drive unit Make sure that the catch locks in place and that the teeth of the C Power LV unit and the drive unit inte...

Страница 12: ...figure 8 chapter 5 1 The display shows settings operating conditions and error messages When no errors are present the display shows the remaining volume of the mounted C Power LV unit in percent volu...

Страница 13: ...ounting device should be used when installing the Timken C Power The lubricant tube must be installed and mounted correctly The length of the lubricant tube should not exceed five meters The tube must...

Страница 14: ...onnections Regularly check the filling level of the transparent C Power LV unit After several additional discharges calculate the reduced discharge period and note it on the lubrication and maintenanc...

Страница 15: ...ion of the remaining discharge period in the lubrication and maintenance schedule 15 Days Average Discharge Volume per Day Weeks Average Discharge Volume per Day Months Average Discharge Volume per Da...

Страница 16: ...h from days to weeks to months within the setting mode by pressing the MODE SAVE button Figure 16 The figures on the display are blinking and the setting mode is shown If you have reached the desired...

Страница 17: ...eviously set mode ON or OFF without saving the changes The original settings remain valid Additional Discharge With an additional discharge a lubrication point can be supplied with an additional amoun...

Страница 18: ...ional discharges with every regular discharge 6 9 Calculation of the Remaining Discharge Period Please note that in case of one or several additional discharges the remaining discharge period of the l...

Страница 19: ...e of the C Power LV Unit Set the size of the C Power LV unit by inserting the contact pin jumper into the base plate of the battery compartment in the drive unit refer to figure 22 Pointed pliers can...

Страница 20: ...and the drive unit interlock The control system will automatically recognize the new C Power LV unit The display will indicate if the Timken C Power was switched off prior to the replacement of the C...

Страница 21: ...Timken C Power distribution block E2 Lubrication system has been shut off Drive mechanism of the distributor is defective Check the coding pins and carry out an initialization E3 Lubrication system ha...

Страница 22: ...low local waste disposal regulations 10 SERVICE Please contact your local Timken distributor for availability and cost of the following Returning an empty lubricator for environmentally safe recycling...

Страница 23: ...cs Connector Where the connecting cable plugs in Connecting piece 6 pcs Used to attach the lubricant tubes Plug 4 pcs Seals outlets that are not used Bores 1 to 6 Where the coding pins are inserted in...

Страница 24: ...des of the lubricator and the distributor are level Attach distributor and lubricator to the mounting device using the four bores Connect lubricant tubes to connecting pieces Position them between the...

Страница 25: ...operating condition Connector for distribution block Connection thread G 3 8 outside and G 1 8 inside for application into a lubrication point or for connecting a grease tube DISPLAY Configuration men...

Страница 26: ...eeth of C Power LV unit and drive unit interlock Turn the cover clockwise until the bayonet catch locks in place 2 Starting the C Power Hold down the ON OFF SELECT button until Remaining Volume appear...

Страница 27: ......

Страница 28: ...www timken com Timken is the registered trademark of The Timken Company 2006 The Timken Company Printed in USA Order No 999 10793...

Отзывы: