background image

16

6.8 

Setting the Discharge Period

The discharge period can be set any time without having to install a new C-Power LV-unit (refer to 
figures 15 to 18) and without having to interrupt operation. The Timken C-Power can be switched on 
or off, because the system switches back to its original operating status after the changes have been 
made. The only difference is the information shown on the display before and after the settings. In the 
following example, the lubricator is switched off. 

You must hold down the buttons until the indication of the display changes.

To reach the configuration menu, hold down the MODE/SAVE button until the display changes.
Then, the lubricator shows the current settings.

Lubricator is switched off 

The figures on the display are blinking and the

Figure 15

current setting mode is shown (e.g. 

15 

Days).

You can now switch from days to weeks to months within the setting mode by pressing the 
MODE/SAVE button.

Figure 16

The figures on the display are blinking and the setting mode is shown.

If you have reached the desired setting mode, push the ON/OFF/SELECT button as many times as it 
takes to set the number of days, weeks or months.

The figures on the display are blinking and gradually increasing with every push of the button. The example shows the setting of days.

Figure 17

When setting the days, you can select a figure between 01 and 30. After 30, the count starts again 
with 01.

When setting the weeks, you can select a figure between 01 and 24. After 24, the count starts again 
with 01.

When setting the months, you can select a figure between 01 and 24, depending on the size of the 
C-Power LV-unit (refer to table 1) and on the position of the jumper. After 24, the count starts again 
with 01.

MODE

SAVE

MODE

SAVE

MODE

SAVE

Config.
Time

Weeks

01

Config.
Time

Days

15

Config.
Time

Months

01

MODE

SAVE

MODE

SAVE

Config.
Time

Days

01

Config.
Time

Days

30

Config.
Time

Days

02

– –

Содержание C-POWER 250

Страница 1: ...Timken C Power Lubricator Operating System Manual...

Страница 2: ......

Страница 3: ...12 5 1 Display Elements 5 2 Function Indication on the Display 5 3 Function Indication via the LED Signal Lights 5 4 Control Buttons 6 Operation and Control 13 6 1 Preparations 6 2 Questions to Ask Pr...

Страница 4: ...me and improve safety 1 1 Delivery Content Timken C Power will be delivered according to customer specifications for type of grease and size of the C Power LV unit The user will only need to assemble...

Страница 5: ...ing addition and or variation is considered inappropriate 1 5 Legal Requirements Liability The information data and tips contained in this operating manual were current as of the printing date No clai...

Страница 6: ...efore any changes are made Only original tube connections and connectors from Timken can be used on or with the lubrication system These will withstand high pressure up to 360 psi 25 bar Ambient media...

Страница 7: ...rease Correct Answer 3 m maximum tube length for standard grease 5 m maximum tube length for low temperature grease arrow 1 meets the dashed line of the standard grease range at 3 m 2 You want to use...

Страница 8: ...ower LV unit which can be supplied in 250 cc and 500 cc versions Lubricant can be requested by the customer Use only Timken C Power LV units Battery set consisting of two batteries The batteries are n...

Страница 9: ...t the lubrication points and the complete lubricant tube are pre lubricated with the same lubricant that is contained in the C Power LV unit To do this Timken offers a 400 g lubrication cartridge for...

Страница 10: ...position of the jumper It must correspond to the size of the C Power LV unit refer to figure 4 and chapter 7 1 Figure 4 b Place the C Power LV unit inside the protection cover and remove the plug refe...

Страница 11: ...r to figure 6 Figure 6 d Place the C Power LV unit with its protection cover on the drive unit Make sure that the catch locks in place and that the teeth of the C Power LV unit and the drive unit inte...

Страница 12: ...figure 8 chapter 5 1 The display shows settings operating conditions and error messages When no errors are present the display shows the remaining volume of the mounted C Power LV unit in percent volu...

Страница 13: ...ounting device should be used when installing the Timken C Power The lubricant tube must be installed and mounted correctly The length of the lubricant tube should not exceed five meters The tube must...

Страница 14: ...onnections Regularly check the filling level of the transparent C Power LV unit After several additional discharges calculate the reduced discharge period and note it on the lubrication and maintenanc...

Страница 15: ...ion of the remaining discharge period in the lubrication and maintenance schedule 15 Days Average Discharge Volume per Day Weeks Average Discharge Volume per Day Months Average Discharge Volume per Da...

Страница 16: ...h from days to weeks to months within the setting mode by pressing the MODE SAVE button Figure 16 The figures on the display are blinking and the setting mode is shown If you have reached the desired...

Страница 17: ...eviously set mode ON or OFF without saving the changes The original settings remain valid Additional Discharge With an additional discharge a lubrication point can be supplied with an additional amoun...

Страница 18: ...ional discharges with every regular discharge 6 9 Calculation of the Remaining Discharge Period Please note that in case of one or several additional discharges the remaining discharge period of the l...

Страница 19: ...e of the C Power LV Unit Set the size of the C Power LV unit by inserting the contact pin jumper into the base plate of the battery compartment in the drive unit refer to figure 22 Pointed pliers can...

Страница 20: ...and the drive unit interlock The control system will automatically recognize the new C Power LV unit The display will indicate if the Timken C Power was switched off prior to the replacement of the C...

Страница 21: ...Timken C Power distribution block E2 Lubrication system has been shut off Drive mechanism of the distributor is defective Check the coding pins and carry out an initialization E3 Lubrication system ha...

Страница 22: ...low local waste disposal regulations 10 SERVICE Please contact your local Timken distributor for availability and cost of the following Returning an empty lubricator for environmentally safe recycling...

Страница 23: ...cs Connector Where the connecting cable plugs in Connecting piece 6 pcs Used to attach the lubricant tubes Plug 4 pcs Seals outlets that are not used Bores 1 to 6 Where the coding pins are inserted in...

Страница 24: ...des of the lubricator and the distributor are level Attach distributor and lubricator to the mounting device using the four bores Connect lubricant tubes to connecting pieces Position them between the...

Страница 25: ...operating condition Connector for distribution block Connection thread G 3 8 outside and G 1 8 inside for application into a lubrication point or for connecting a grease tube DISPLAY Configuration men...

Страница 26: ...eeth of C Power LV unit and drive unit interlock Turn the cover clockwise until the bayonet catch locks in place 2 Starting the C Power Hold down the ON OFF SELECT button until Remaining Volume appear...

Страница 27: ......

Страница 28: ...www timken com Timken is the registered trademark of The Timken Company 2006 The Timken Company Printed in USA Order No 999 10793...

Отзывы: