7. Setting Up

Walk Test Procedure (Test Mode)

•  Make sure the PIR sensor is set to Test Mode i.e. the TIME ON Adjustment  

to the minimum (fully anti-clockwise), and the Lux Level set the Sun symbol 
(fully clockwise). 

•  Turn the power to the unit ON. The lamp will immediately illuminate as the unit 

goes through its ‘warm-up’ period. After approximately 30 seconds the lamp will 
extinguish. This indicates the unit is wired correctly and the unit is in Test Mode. 

•  Try to remain outside the detection area during the warm-up period.

•  The unit will now operate during daytime as well as at night, illuminating the 

lamp for approx. 2 seconds each time. This allows testing to be carried out  
to establish whether the sensor is covering the required area.

•  Walk across the location the sensor is fitted, to establish the detection zone.

•  The sensor will detect you approximately up to 12 metres forward at mounting 

height of 2.5m.

•  As you cross a detection ‘zone’ the lamp will illuminate. Now stand still  

until the lamp extinguishes (this should take approx. 2 seconds).

•  Start moving again after 5 seconds.  

Each time you cross the detection  
‘zone’ the lamp will illuminate.

•  Repeat the above, walking at various  

distances and angles to the unit.  
This will help you to confirm the  
detection pattern (See image 10).

10

Содержание MLTP180BK

Страница 1: ...I n s t a l l a t i o n O p e r a t i n g I n s t r u c t i o n s 180 Tamper proof Wall Mounted PIR Model MLTP180BK Black Model MLTP180WH White...

Страница 2: ...ding when this PIR sensor is fitted does not exceed the rating of the circuit cable fuse or circuit breaker 3 Technical Specifications 230V AC 50 Hz This PIR sensor is of Class II Construction and mus...

Страница 3: ...ment ACROSS its field of vision than to movement directly TOWARDS Therefore position the unit so that the sensor looks ACROSS the likely approach path Avoid positioning the sensor where there are any...

Страница 4: ...ble the power to be switched ON and OFF for maintenance purposes and to activate the manual auto override function 5 3 Use a 2 5mm Allen key to unlock the captive latch located on the bottom of the se...

Страница 5: ...s or electrical cables that may be hidden below the surface Insert the rawl plugs into the holes 5 7 Pass the 230V 50Hz supply and load cables through the cable entry points on the back box ensuring t...

Страница 6: ...ing See image 7 5 10 Position the PIR sensor over the back box making sure the adjustments are located on the bottom and secure using the 4x fixing screws previously removed in step 5 5 See image 9 5...

Страница 7: ...ction Diagram Connect the cables to the terminal block as follows 230V 50Hz Mains Supply Live Supply Brown or Red to L Neutral Supply Blue or Black to N A Loop Terminal is provided should a 3 core cab...

Страница 8: ...erate during daytime as well as at night illuminating the lamp for approx 2 seconds each time This allows testing to be carried out to establish whether the sensor is covering the required area Walk a...

Страница 9: ...Level adjustment knob fully clockwise Sun symbol 2 When the ambient light level reaches the level of darkness at which you wish the lamp to become operative i e at dusk SLOWLY rotate the control in an...

Страница 10: ...d ON for longer time periods by use of the Manual Override Mode This can be activated at night time only by using the internal wall switch or circuit breaker Switch the internal wall switch twice OFF...

Страница 11: ...cases For all eligible replacements where agreed by Timeguard the customer is responsible for all shipping postage charges outside of the UK All shipping costs are to be paid in advance before a repla...

Страница 12: ...csc timeguard com For a product brochure please contact If you experience problems do not immediately return the unit to the store Telephone the Timeguard Customer Helpline Qualified Customer Support...

Отзывы: