5
Programming
Each Rx unit needs to learn the codes involved in the
messages from all the Tx units which are required to
control it (up to 20).
** If introducing the TLTXK2 hand held transmitter press
the “1” button on this unit to activate the
TLRX150B/500B
.
***If the button is pressed for 5 seconds or more then all
the codes that have been learnt will be erased.
1
2
3
4
Turn OFF/remove batteries from any Tx unit which is not
required to control this RX unit. Turn off any other Rx units.
If it is convenient more than one Rx unit can learn the code of
a Tx unit simultaneously in which case leave these Rx units
switched ON.*
The Rx unit needs to be set in programme mode. This will
happen automatically up to 4 seconds after the Rx unit is first
powered up. It can also be set by pressing the Programme/
Reset button for 1 to 2 seconds (pressing for 5 seconds or
longer will erase all programming within the Rx unit). In either
case the Time On/Test control must be set to Test which will
give a 5 minute period of programme mode. The lights under
control of the Rx unit will turn on at the start of this period
indicating it is in progress.
Go to the Tx unit** to be introduced to the Rx unit and
move across the face of its PIR lens within detection
range causing it to detect (indicated by the lights under
control turning ON for most Tx units and by a flash from
the red LED on the TLTXDCB.
Return to the Rx unit and check that it has turned the
lamps under its control off (indicating correct code learning).
*Any other Rx units left connected should now be
checked in the same way.
Press the Programme/Reset button for 1 to 2 seconds*** if
the Rx unit is required to learn the code of another Tx unit.
*Any other Rx units required to learn the code of this
new Tx unit should be left connected.
iTLRX150B_500B_Instructions.qxd 1/19/05 12:05 PM Page 6