6.4.4

 

Electronic Drives 

 

When used with electronic drives such as motor accelera- 
tors, solid state starters, variable frequency drives, etc., an 
isolating contactor must be installed between the motor 
and the electronic drive device to protect the electronic 
drive. 

 

The coil of the contactor must be interlocked with Termi- 
nals 3 and 4 of the SHORT-STOP; see Figs. 6.1 to 6.3. 

 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 6.4.4  With Electronic Drives 

 

6.4.5

 

Single Phase 

 

Refer to Fig. 6.4.1 (Single Direction, Single Speed.) Use 
L1 & L2, rather than L1 & L3 for the power source. 

 

Note that for a given voltage and horsepower rating, a 
single-phase machine will draw greater current than the 
three-phase equivalent. Be sure not to exceed either the 
horsepower or current rating of the SHORT-STOP. 

 

7.

 

OPTIONS 

7.1

 

Programmable Controller Mode 

 

If your motor starter is controlled by a programmable 
controller or other type of solid state switch, or if the 
electronic brake does not activate after the motor has been 
run, then: 

 

 

a.

 

Connect Terminals S and W to a dry normally open 
(N/O) auxiliary contact on all starter contactors. 

 

b.

 

Set the "ILK SENSE" switch (located to the right of the 
brake LED on the control board) to the OFF position. 

 

7.2

 

Option L (45 sec. max. braking time.) 

Maximum braking time is 45 seconds. No additional 
wiring or controls involved. (Other braking times are also 
available) 

 

7.3

 

Option S (Higher Torque) 

 

The maximum braking torque is higher than for standard 
models. No additional wiring or controls are involved. 

 

7.4

 

Option BD / Y (Brake Disable/Timeout) 

 

Permits the brake to be disabled for certain purposes, such 
as jogging or setup. To use this option, connect a DRY 
contact or switch to Terminals B and Y. If the switch or 
contact is closed during the run to brake transition, no 
brake cycle will follow (motor coasts to a stop). If the 
switch or contact is closed during a brake cycle, the brake 
cycle will be terminated. 

 

7.5

 

Option D (Dual-voltage operation) 

 

On "dual-voltage" rated units, permits a single SHORT- 
STOP to be used on either 230 OR 460 volts. 

 

7.6

 

Option R (Braking using 3 motor windings) 

 

May be used to excite all three windings. With this option, 
the third motor lead is connected to Terminal 7. All other 
connections are made as described for standard units. 

Содержание AMBITECH SHORT-STOP G

Страница 1: ...SHORT STOP Electronic Motor Brake Type G Instructions and Setup Manual...

Страница 2: ...IONS 5 7 1 Programmable Controller Mode 5 7 2 Option L 45 sec max braking time 5 7 3 Option S Higher Torque 5 7 4 Option BD Y Brake Disable Timeout 5 7 5 Option D Dual voltage operation 5 7 6 Option R...

Страница 3: ...t only dangerous but can cause damage not covered by the warranty POWER LINE INTERRUPTION The SHORT STOP uses AC line power to achieve its braking action Thus a power failure or disconnect or the open...

Страница 4: ...sources of vibration dust dirt and extremes of temperature Once mounted it normally needs no maintenance 6 2 Wiring ALL WIRING SHOULD CONFORM WITHNATIONAL AND LOCAL ELECTRICAL CODES Terminals 3 and 4...

Страница 5: ...ectly connected and the mandatory test has been passed successfully the power wiring may be done As shown in the circuit diagrams below and on the typical wiring diagram inside the SHORT STOP enclosur...

Страница 6: ...then a Connect Terminals S and W to a dry normally open N O auxiliary contact on all starter contactors b Set the ILK SENSE switch located to the right of the brake LED on the control board to the OFF...

Страница 7: ...1 Set TIME control located on the logic board to the left of the brake LED to mid range 2 Set TORQUE control located on the phase shift board below the fuses to minimum Full counter clockwise 3 Turn m...

Страница 8: ...erly the following checks should be made A Check that TIME and TORQUE controls are set properly and are not at minimum B Verify that the SHORT STOP rated motor voltage is present at Terminals 5 and 6...

Страница 9: ...mber Model Number and to list all options provided 4 PACK THE UNIT CAREFULLY so that there will be no further damage during shipment 5 Be sure to include your name address telephone number and the add...

Отзывы: