FUNCTION CHARACTERISTICS
80
NA30 - Manual - 04 - 2022
Residual overvoltage - 59N
Preface
Two operation thresholds, independently adjustable (
U
E
>,
U
E
>>) with adjustable delay (
t
UE
>,
t
UE
>>).
The first one (
U
E
>) may be programmed with definite or inverse time, while the second threshold
operates with definite time characteristic.
Each threshold may be separately enabled or disabled.
The first threshold trip (
U
E
>) may be inhibited by start of the second threshold (
U
E
>>).
Operation and settings
The residual voltage (
U
E
) is compared with the setting values (
U
E
>,
U
E
>>); a start is issued when the
residual voltage overcomes the adjustable threshold (START); after expiry of the associated operate
time (
t
UE
>,
t
UE
>>) a trip command is issued; if instead the voltage drops below the threshold, the
element is restored.
The first threshold (
U
E
>) may be programmed with definite or inverse time according the following
characteristic curve:
t
=0.5
t
UE
> / [(
U
E
/
U
E
>
inv
) - 1] or
Where:
U
E
:
measured residual voltage
t
:
operate time
U
E
>
inv
:
threshold setting
t
UE>inv
:
operate time setting
For the inverse time characteristic, following data applies:
• The operate time setting is referred to an input voltage equal to 1.5 of the pickup value.
• Asymptotic reference value (minimum pickup value): 1.1
U
E
>
inv
• Minimum operate time: 0.1
s
• Range where the equation is valid: 1.1 ≤
U
E
/
U
E
>
inv
≤ 4
• If
U
E
>
inv
pickup ≥ 0.5
U
En
, the upper limit is 2
U
En
.
The first residual overvoltage element can be programmed with definite or inverse time character-
istic by setting the
UE> Curve
parameter (
DEFINITE, INVERSE
) available inside the
Set \ Profile
A(or B) \ Residual overvoltage-59N \
UE
> Element \ Setpoints
menu.
Each element can be enabled or disabled by setting
ON
or
OFF
the
UE> Enable
parameter inside
the
Set \ Profile A(or B) \ Residual overvoltage-59N \
UE
> Element \ Setpoints
menu and/or the
State
parameter inside the
Set \ Profile A(or B) \ Residual overvoltage-59N \
UE
>> Element \ Definite time
.
For both elements, a block of the
U
E
> and
U
E
>> threshold may be select when the 74VT function is
active (external). The blocking enabling parameters
74VText59N
is available inside the
Set \ Pro-
file A(or B) \ Residual overvoltage-59N \
Common
configuration
menu.
[1]
The first threshold trip (
U
E
>) may be inhibited by start of the second threshold (
U
E
>>) by setting
ON
the UE> Disabling by UE>> start (
UE>disbyUE>>
) parameter available inside the
Set \ Profile A(or
B) \ Residual overvoltage-59N \ UE>> Element \ Setpoints
menu.
Note 1 The operating time must be adjusted to a greater value than the 74VT activation time (internal or binary input)
t-int-F59N.ai
U
E
U
E
>>
t
UE
>
t
UE
>>
U
E
>
t
TRIP
General operation time characteristic for the residual overvoltage elements - 59N