Technical Data
Cable Specifications
Operating voltage: 230V 50Hz
Power consumption: <10W
Maximum number of SENSALINK SENLPS G per
installation: 99
Maximum number of devices per SENSALINK
SENLPS G: 200 (SENSALINK WHI MW SENLCP and
SENSALINK RS MW SENLCP count twice each)
Maximum total length of Bus cable (ring topology):
1500m
Dimensions (w x d x h): 213 x 185 x 117mm
IP rating: 65
Spine/Backbone cable: 2x2x0.2mm , twisted pair,
screened communicating cable, eg RS-232 computer
cable, maximum length 1200mm.
SensaLink Digital Bus cable: 1.5mm mains rated
unscreened twisted-pair.
2
2
All On Full -
Load Shed 1 -
Load Shed 2 -
This command affects every device on the
SensaLink Bus.
Use a latching normally-open switch. When the switch is
made, all devices turn on at full brightness. The devices
will go to their ‘Entry Scene’ no later than 30 seconds after
the switch is released. Please note this function is also
available via a keyswitch on the front panel.
This command is addressed to each
device on the SensaLink Bus that has been programmed
to ‘Global Address 1 Rx: YES’.
Use a latching normally-open switch. When the switch is
made, all relevant devices turn off. The devices will begin
responding the movement again (go to their ‘Entry Scene’
if the area is occupied) no later than 30 seconds after the
switch is released.
This command is addressed to each
device on the SensaLink Bus that has been programmed
to ‘Global Address 2 Rx: YES’.
Use a latching normally-open switch. When the switch is
made, all relevant devices turn off. The devices will begin
responding the movement again (go to their ‘Entry Scene’
if the area is occupied) no later then 30 seconds after the
switch is released.
Front Panel
The status of each switch at any given time is indicated
through five green LEDs located on the front panel of the
SENSALINK SENLPS G. They illuminate only when the
switch associated with each command is closed. The
LEDs go out instantly when the switch is opened although
the actual command may still be active on the bus for up to
30 seconds.
The ‘All On Full’ command can be instigated
via
keyswitch next to the LED array.
The red Power LED will illuminate when mains power is
applied to the unit.
The colourless Activity LED flashes green only when there
is activity in any zone on the bus. It flashes red when a bus
installation fault is detected regardless of movement or
occupancy in the building. Please note that not all faults
will be indicated by this LED.
The yellow Linking LED will flash when multiple
SENSALINK SENLPS Gs are connected together and
Common Zone 1 linking occurs.
Installation and Commissioning
Instructions
SENSALINK SENLPS G (96232305)
SensaLink Bus Power Supply Global
(formerly known as SLKGPSU)
W4134I
Override Inputs
Three pairs of switch input terminals located behind the
lower housing cover enable easy control of complete
systems from one centralised location. Inputs require a
latching, normally-open switch or a momentary, push-to-
make switch as appropriate:-