![THORLABS LNR502E Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/thorlabs/lnr502e/lnr502e_user-manual_1110766016.webp)
Page 14
ETN053047-D02
LNR502E Encoded Long Travel, Linear Stage with Stepper Motor Actuator
2) Select the Advanced tab.
Fig. 4.5 Settings - Advanced tab
3) In the
PID Loop Mode
field, select Closed Loop.
4) Encoder feedback is now enabled.
When Closed Loop is selected, the motion processor within the controller uses a position control loop to determine the motor
command output. The purpose of the position loop is to match the actual motor position and the demanded position. This is
achieved by comparing the demanded position with the actual position to create a position error, which is then passed through
a digital PID-type filter. The filtered value is the motor command output.
The default PID parameters should be sufficient for most applications, but these can be fine tuned to improve performance as
required by creating Custom settings - see the manual for the associated controller and also the Kinesis helpfile for further
information on creating custom settings.
The parameters on the settings panel are described as follws:
Proportional Gain
- Together with the Integral and Differential, these terms determine the system response characteristics and
accept values in the range 0 to 16777216.
Integral
Gain
- Together with the Proportional and Differential, these terms determine the system response characteristics and
accept values in the range 0 to 16777216.
Differential
Gain
- Together with the Proportional and Integral, these terms determine the system response characteristics and
accept values in the range 0 to 16777216.
Integral Limit
- This parameter is used to cap the value of the PID loop to prevent runaway at the output. It accepts values in
the range 0 to 16777216. If set to 0 then the output of the PID loop is ignored.
Tolerance
- Value below which the output of PID generator is effectively deemed to be zero to avoid continual cycle about set
point
Encoder Coefficient
- This is a conversion factor from Encoder counts to microsteps for the specific stage and controller being
used. For the BSC series controllers and LNR50SE stage, the value is 4292282941. If set to 0, then no encoder is fitted to the
stage.
Содержание LNR502E
Страница 9: ...Rev A Apr 2020 Page 7 Chapter 3 Installation Fig 3 3 Fitting the Y Axis Stage 5 4 6 ...
Страница 31: ...Rev A Apr 2020 Page 29 Chapter 8 Thorlabs Worldwide Contacts ...
Страница 32: ...Page 30 ETN053047 D02 LNR502E Encoded Long Travel Linear Stage with Stepper Motor Actuator ...
Страница 33: ...Rev A Apr 2020 Page 31 Chapter 8 Thorlabs Worldwide Contacts ...
Страница 34: ...Page 32 ETN053047 D02 LNR502E Encoded Long Travel Linear Stage with Stepper Motor Actuator ...
Страница 35: ...Rev A Apr 2020 Page 33 Chapter 8 Thorlabs Worldwide Contacts ...
Страница 36: ...Page 34 ETN053047 D02 LNR502E Encoded Long Travel Linear Stage with Stepper Motor Actuator ...
Страница 37: ...Rev A Apr 2020 Page 35 Chapter 8 Thorlabs Worldwide Contacts ...
Страница 38: ...Page 36 ETN053047 D02 LNR502E Encoded Long Travel Linear Stage with Stepper Motor Actuator ...
Страница 39: ...Rev A Apr 2020 Page 37 Chapter 8 Thorlabs Worldwide Contacts ...
Страница 40: ...Page 38 ETN053047 D02 LNR502E Encoded Long Travel Linear Stage with Stepper Motor Actuator ...
Страница 41: ...Rev A Apr 2020 Page 39 Chapter 8 Thorlabs Worldwide Contacts ...
Страница 42: ...Page 40 ETN053047 D02 LNR502E Encoded Long Travel Linear Stage with Stepper Motor Actuator ...
Страница 43: ...Rev A Apr 2020 Page 41 Chapter 8 Thorlabs Worldwide Contacts ...
Страница 44: ...Page 42 ETN053047 D02 LNR502E Encoded Long Travel Linear Stage with Stepper Motor Actuator ...
Страница 45: ...www thorlabs com ...