Maintenance Service and Trouble Shooting

 

C. Sudden stop of Compressor during Its Running 
The cause of sudden stop of a compressor during its running is mostly that the gas 
suction pressure and/or discharge pressure exceed their respective prescribed ranges, 
thus making a pressure-operated protective relay shut off the power to the compressor 
and stop it. In the following we discuss mainly the reasons for causing excessively high 
gas discharge pressure and low suction pressure. 
 
1)  Stoppage due to excessively high gas discharge pressure   
a) Too much refrigerant charged into the system   
Analysis of Trouble 
The phenomenon, such as loose frosting and poor refrigerating effect, may occur if 
excessive refrigerant has been charged into the system. Superfluous refrigerant will 
occupy a certain space of the evaporator, thus reduce its heat dissipating area, and the 
phenomenon of "liquid striking" may occur, too. Meanwhile, dew or frost condensation 
may occur on the gas return tube, and the gas discharge pressure will obviously rise, 
when it reaches the threshold value, the protective relay will actuate and shut off the 
power supply to the compressor. 
 
Remedy 
Open the tubing, re-evacuate and then charge the system with a proper quantity of 
refrigerant. 
 
b) Air left in the system 
Analysis of Trouble 
The residual air in the system will circulate together with the refrigerant in the system. 
The major symptoms caused by this residual air is higher gas discharge pressure, 
higher discharged gas temperature (the gas discharge tubing is considerably hot when 
you feel it with your hand), and poorer refrigerating effect. Furthermore, the gas 
discharge pressure will exceed its normal value when the compressor has run for a 
period not too long, thus making the protective relay actuate and bring to a stoppage. 
 
Remedy 
Check up how the air has been left in the refrigerating system. Generally, there are two 
possibilities: one is that the air has been sucked into the system when repairing due to 
carelessness, or it has not been purged out totally when evacuating the system; the 
other is that there are leak points at the low pressure end of the refrigerating system. 
Leak points appear mostly in those low temperature parts or assemblies, because the 
evaporation temperature is lower for such low temperature devices, especially at the 
low pressure end, it is easier for the air goes into the system. Once it has been 
ascertained that air does exist in the system, you have to open the tubing, re-evacuate 
it and then charge it with refrigerant. 
 
2)  Stoppage due to electric troubles   
a) Thermostat is out of control   
Analysis of Trouble 
In case the thermostat does not work in      its good order or its temperature sensor has 
not been installed properly, frequent stoppage is also likely to occur. 
 
 

22 

Содержание TWC2403DI

Страница 1: ...Wine Cooler Service Manual Models TWC2403DI Features Energy efficiency Micro foam technology Low noise operation Thick insulation for enerqv efficiency Version number 00 00 Edition 2019 5 20...

Страница 2: ...1 CONTENT 1 Content 2 2 Specifications 3 3 Safety precautions 4 4 Function Schedule 7 5 System Flow Chart 8 6 Circuit Diagram 9 7 Maintenance Service and Trouble Shooting 10 8 List of Parts 28 2...

Страница 3: ...Color Black Power Supply V Hz 110 60 Rated Input Power W 370 Power Consumption kW h 24h 1 3 Net Weight Lbs 264 Gross Weight Lbs 286 Unit Dimension 60 68 5 187 W D H CM Packing Dimension W D H CM 66 7...

Страница 4: ......

Страница 5: ......

Страница 6: ......

Страница 7: ...Function Page Function Schedule Energy efficiency Micro foam technology Low noise operation Thick insulation for energy efficiency 7...

Страница 8: ...low Chart 2 Brief Description of System Flow Chart Model TWC2403DI is a fan cooling double system wine cooler When the wine cooler is just powered on the refrigerant flows in the sequence Compressor C...

Страница 9: ...n of Control Principle Model TWC2403DI is the direct cooling double system Wine Cooler an electronic type of all the control is generally adopted The display control PCB directly controls the start an...

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ...refrigerator This is a normal sound produced by the pull in or release of the armature of a current deadweight start relay when starting the compressor The compressor motor will produce a slight and...

Страница 14: ...ious welding points for leaks if leakage occurs an oil stain can be seen definitely b Check the suction and exhaust pressure values high pressure and low pressure of compressor to see whether they are...

Страница 15: ...er the compressor has operated normally for 5 10 minutes Touch and feel the condenser the temperature of its upper part should be higher than that of its lower part or its right part is hotter than it...

Страница 16: ...outlet of the capillary and no frost or a smaller quantity of loose frost appears on the evaporator After shut down the balance pressure in the system is usually lower than the saturation pressure cor...

Страница 17: ...utes open the tubing evacuate it and then recharge the system with refrigerant 4 Low efficiency of compressor Analysis of Trouble Low efficiency of a refrigerating compressor refers to the actual redu...

Страница 18: ...left in the evaporator Dismantle the evaporator purge it thoroughly and then dry it In case it is difficult to dismantle it charge refrigerant from the evaporator inlet to wash it several times then p...

Страница 19: ...gerating system has been performed improperly the effect of air purging for the whole system is not good or the water content in the refrigerant is out of standard all these will cause the expansion v...

Страница 20: ...s been used for a longer time or by the dirt accumulated gradually inside the filter Sometimes tapping the filter nay cause a passage for flowing touching it with your hand you will feel that it is co...

Страница 21: ...rouble The residual air in the system will circulate together with the refrigerant in the system The major symptoms caused by this residual air is higher gas discharge pressure higher discharged gas t...

Страница 22: ...w one 3 Sudden stoppage due to other causes Normal Stoppage Start and stop of the compressor is generally controlled by a thermostat When the temperature in the refrigerator reaches its desired value...

Страница 23: ...re sensor Remedy Remove the relay cover to check up its contacts if they are open this means that the original setting is not properly set or temperature sensing agent has leaked out of the temperatur...

Страница 24: ...upply Dirt and other impurities in the lubricant oil will increase its viscosity and cause the shaft to be seized Copper plating may also result in seizing of shaft b Seizing of piston This is caused...

Страница 25: ...temperature cannot reach its rated value the thermostat won t work thus the compressor runs continuously When the evaporation temperature in the system is too high the temperature sensing agent in th...

Страница 26: ...handle or other metal parts with your hand Test the refrigerator with a test pencil it will light up intensively measure the resistance between the power cord plug and the case body with an avometer...

Страница 27: ...ecomes weaker or vanishes If the refrigerator has not been levelly placed put a level meter on its top table and adjust the leveling screws on its legs In case noise occurs from the compressor strike...

Отзывы: