TS 910 TRANSFER SWITCH
PM140 REV 0 12/02/09
44
Thomson Technology
30 seconds or 60 seconds. A jumper must be placed across the 2 pins,
adjacent to the desired time as shown on the PCB.
Refer to Section 18.15.1 for the factory default settings of the Engine Warm-up
Delay timer
18.15.7.
ENGINE COOL DOWN DELAY JUMPERS
A TSC 9 PCB mounted jumper is provided to configure the desired Engine Cool
down Delay timer settings. Three time settings are provided – 1 minute, 2
minutes or 5 minutes. A jumper must be placed across the 2 pins, adjacent to
the desired time as shown on the PCB.
Refer to Section 18.15.1 for the factory default settings of the Engine Cool down
Delay timer
18.15.8.
UTILITY RETURN DELAY JUMPERS
A TSC 9 PCB mounted jumper is provided to configure the desired Utility Return
Delay timer settings. Three time settings are provided – 10 seconds, 60 seconds
or 120 seconds. A jumper must be placed across the 2 pins, adjacent to the
desired time as shown on the PCB.
Refer to Section 18.15.1 for the factory default settings of the Utility Return
Delay timer
18.15.9.
CURRENT TRANSFORMER SIZE JUMPERS
A TSC 9 PCB mounted jumper is provided to configure the size of current
transformers which are utilized when the kW Load shed option is used with the
transfer switch. When the kW Load shed option is not used, no jumper setting is
required. Additional information on TS 910 kW Load shed optional accessory can be
obtained from our Website (
www.thomsontechnology.com
).