![THOMSON marathon TS 910 Series Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/thomson/marathon-ts-910-series/marathon-ts-910-series_owners-manual_1110065021.webp)
TS 910 TRANSFER SWITCH
PM140 REV 0 12/02/09
15
Thomson Technology
9.
RECOMMENDED MAINTENANCE
DANGER!!!!
Arc Flash and Shock Hazard. Will cause severe injury or death.
Do not open equipment until ALL power sources are disconnected
This equipment must be installed and serviced only by qualified electrical
personnel utilizing safe work practices and appropriate Personal Protective
Equipment (PPE). Failure to do so may cause personal injury or death
10.1.
DO NOT perform dielectric tests on the equipment with the control components in the
circuit.
10.2.
Check if control components are tight in sockets.
10.3.
Periodically inspect all terminals (load, line and control) for tightness. Re-torque all
bolts, nuts and other hardware. Clean or replace any contact surfaces, which are
dirty, corroded or pitted.
10.4.
Transfer switches should be in a clean, dry and moderately warm location. If signs of
moisture are present, dry and clean transfer switch. If there is corrosion, try to clean
it off. If cleaning is unsuitable, replace the corroded parts. Should dust and/or debris
gather on the transfer switch, brush, vacuum, or wipe clean. DO NOT blow dirt into
power switching devices.
10.5.
Test the transfer switch operation. While the unit is exercising, check for freedom of
movement, hidden dirt, corrosion or any excessive wear on the mechanical operating
parts.
10.6.
Verify all settings on the TSC 9 controller as per the TSC 9 component calibration
label inside the transfer switch enclosure.