![THOMSON marathon TS 910 Series Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/thomson/marathon-ts-910-series/marathon-ts-910-series_owners-manual_1110065028.webp)
TS 910 TRANSFER SWITCH
PM140 REV 0 12/02/09
22
Thomson Technology
16. ENCLOSURE DIMENSIONS/CABLE TERMINALS
DIMENSIONS
TERMINAL RATING
MODEL
TYPE
AMPERAGE
HEIGHT
INCHES
WIDTH
INCHES
DEPTH
INCHES
SHIPPING
WEIGHT
LBS
QTY
PER
PHASE
RANGE
TS912A0100A
STD ATS
100A
16 1/8"
18 7/8"
8 1/4"
20 lbs
1
#14 - 1/0
TS912A0100B
SE ATS
100A
27 1/8"
18 7/8"
8 1/4"
30 lbs
1
#14 - 1/0
TS912A0200A
STD ATS
200A
27 1/8"
18 7/8"
8 1/4"
30 lbs
1
#6 - 250mcm
TS912A0200B
SE ATS
200A
31 1/8"
18 7/8"
8 1/4"
35 lbs
1
#6 - 250mcm
TS912A0400A
STD ATS
400A
45 1/8"
24 7/8"
11"
70 lbs
2
#6 - 250mcm
TS912A0400B
SE ATS
400A
45 1/8"
24 7/8"
11"
80 lbs
2
#6 - 250mcm
17. REQUIREMENTS FOR UPSTREAM CIRCUIT PROTECTIVE DEVICES
17.1.
TRANSFER SWITCH WITHSTAND CURRENT RATINGS
WITHSTAND CURRENT RATING AMPS (RMS)
With Upstream
Circuit Breaker
Protection
With Upstream Fuse
Protection
MODEL
MAX.
VOLTAGE
RATED
CURRENT
(A)
@240V
@ Up to
240V
Fuse Type
TS912A0100A
240
100
10,000
100,000
T, J
TS912A0200A
240
200
10,000
100,000
T, J
TS912A0400A
240
400
25,000
100,000
T, J
Fuse ratings shown are maximum allowable to permit use of the transfer switch in application
with available fault current not exceeding that shown. Consideration must be given to fuse
sizing when fuses also provide overload protection.
Содержание marathon TS 910 Series
Страница 2: ......
Страница 6: ......
Страница 53: ...TS 910 TRANSFER SWITCH PM140 REV 0 12 02 09 47 Thomson Technology 19 TS 910 SCHEMATIC DIAGRAM ...
Страница 57: ...TS 910 TRANSFER SWITCH PM140 REV 0 12 02 09 51 Thomson Technology 23 NOTES ...