![Thinget XC-E4AD2DA Скачать руководство пользователя страница 67](http://html1.mh-extra.com/html/thinget/xc-e4ad2da/xc-e4ad2da_operators-manual_1106980067.webp)
Modules
Channels No.
0CH to 1CH
1#modules
D8250
2#modules
D8254
3#modules
D8258
4#modules
D8262
5#modules
D8264
6#modules
D8268
7#modules
D8272
Note: As show in the preceding table, each register set 2 channels’ mode, each register has 16 bits, from low
bit to high bit, every 4 bits set 2 channels’ mode.
Take the first module as an example:
Register FD8250:
Channel 1
Channel 0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
-
0:voltage
output
0:0 to
10V
1:0 to 5V
-
0:voltage
output
1:current
output
0:0 to
20mA
1:4 to
20mA
1:current
output
3.
External connection
When carry on exterior connection, please note the following two items:
●
When connect with ex24V power supply, please use 24V power supply on PLC main unit to avoid
intefere.
●
To avoid intefere, please use shield cable, and single-point grounding with the shield layer.
●
Module’s 0 to20 mA or 4 to 20mA output should be offered 24V power supply from outside. According to
the OD value. Adjust the circuit’s current. The module itself doesn’t generate current.
Take 1# module as a example:
FD8250 H 0 0 0 0
0CH