Register FD8251
:
E.g.
:
1
)
Set module 1’s No. 3
、
No.2
、
No.1
、
No.0 channel’s working mode separately as
0~20mA
、
4~20mA
、
0~20mA
、
4~20mA, filters are all 1/2 filter, data in FD8250 is 0101H
2
)
Set module 1’s No. 7
、
No.6
、
No.5
、
No.4 channel’s working mode separately as
0~10V
、
0~5V
、
0~10V
、
0~5V, all the four channels don’t filter, data in FD8251 is 4545H
4
.
Exterior connection
About exterior connection, you should note the following two items:
When connect
+
24V power outside, please use the 24V power on PLC main unit to avoid interfere.
To avoid interfere, please use the shield cable and single point grounding with the shield layer.
Layout chart:
Channel 1
Channel 0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
00
:
1/2 filter
01
:
not filter
10
:
1/3 filter
11
:
1/4 filter
-
0
:
0~20mA
1
:
4~20mA
00
:
1/2 filter
01
:
not filter
10
:
1/3 filter
11
:
1/4 filter
-
0
:
0~20mA
1
:
4~20mA
-
-
Channel
3
Channel
2
Bit15
Bit14
Bit13
Bit12
Bit11
Bit10
Bit9
Bit8
00
:
1/2 filter
01
:
not filter
10
:
1/3 filter
11
:
1/4 filter
-
0
:
0~20mA
1
:
4~20mA
00
:
1/2 filter
01
:
not filter
10
:
1/3 filter
11
:
1/4 filter
-
0
:
0~20mA
1
:
4~20mA
-
-
Channel 5
Channel 4
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
00
:
1/2 filter
01
:
not filter
10
:
1/3 filter
11
:
1/4 filter
-
0
:
0~10V
1
:
0~5V
00
:
1/2 filter
01
:
not filter
10
:
1/3 filter
11
:
1/4 filter
-
0
:
0~10V
1
:
0~5V
-
-
Channel
7
Channel
6
Bit15
Bit14
Bit13
Bit12
Bit11
Bit10
Bit9
Bit8
00
:
1/2 filter
01
:
not filter
10
:
1/3 filter
11
:
1/4 filter
-
0
:
0~10V
1
:
0~5V
00
:
1/2 filter
01
:
not filter
10
:
1/3 filter
11
:
1/4 filter
-
0
:
0~10V
1
:
0~5V
-
-