Channel
AD signal
PID output
value
PID start/stop
control bit
The set value
PID parameter
:
Kp
、
Ki
、
Kd
、
contr
ol bound
Diff 、
dead
bound
Death
0CH
ID700
ID704
Y700
QD702
Kp
:
QD706
Ki
:
QD707
Kd
:
QD708
Diff
:
QD709
Death
:
QD710
1CH
ID701
ID705
Y701
QD703
2CH
ID702
ID706
Y702
QD704
3CH
ID703
ID707
Y703
QD705
Channel
DA signal
-
-
-
-
4CH
QD700
-
-
-
5CH
QD701
-
-
-
Description
:
Start signal
(
Y
):
When Y is 0, close PID control; when being 1, start PID control
Parameter
P:
proportion parameter, mainly reflect system’s difference,
control as soon as difference
occurs to
decrease this difference.
Parameter
I:
Integral parameter, mainly used to remove the whisht and improve the system’s no
difference degree
Parameter
D:
differential parameter, mainly control signal’s changing trend and decrease the system’s
shake.
Temp. control bound
Diff :
in the assigned bound, carry on PID control, beyond that bound, no PID
control
Each parameter’s reference value
:
Kp=20~100
;
Ki=5~20
;
Kd=200~700
;
DIFF=100~200
3.
Setting of working mode
1
)
Expansion’s input/output all have options of voltage 0~5V
、
0~10V, current 0~20mA
、
4~20mA modes.
Via setting of special FLASH data register FD in PLC. See the following table: