MANUFACTURER SETTINGS (E)
FUNCTION
NO.
FUNCTION
NAME
SETTING
UNIT
SETTING
RANGE
MANUFACTURER
SETTING
1
FILLING FEEDER
TIME
minutes
5 - 20
11*
2
PELLETS IGNITION
TIME
minutes
1 - 15
6*
3
FAN POWER
(IGNITION)
%
5 - 50
15
4
PELLETS DOSE
(IGNITION)
g
50 - 500
320
5
FEEDER
PERFORMANCE
kg/h
5.0 – 45.0
20.0
6
PELLETS FEEDING
PERIOD
seconds
10 - 60
20
7
OVERFLOW AIR
(WORK)
multiplier
0.2 - 2
1
8
OVERFLOW AIR
(MAINTAIN)
multiplier
0.2 - 2
1
9
FLAME DETECTOR
TRESHOLD
%
5 – 90
10
10
FURNACE PROTECTION
(OVERHEAT)
ºC
60 - 90
80*
11
STB TEMPERATURE
ºC
60 – 110
90**
12
IGNITION STABILIZATION
Seconds
0 - 250
90
13
MAXIMUM BURNER POWER
KW
30 – 250
50***
14
MINIMUM BURNER POWER
KW
2 – 50
9
15
MINIMUM FURNACE
TEMPERATURE
ºC
20 – 60
35
16
SENSOR TYPE
KTY / PT
KTY
17
EXTERNAL CONTROL
-
Yes / No
No
18
TEMPERATURE
CALIBRATION
ºC
- 10.0 – 10.0
0.0
*If PT (PT 1000) sensor type is chosen then the range of "STB TEMPERATURE” is 60-
200
o
C
**If PT (PT 1000) sensor type is chosen then the range of "STB TEMPERATURE” is 90-
250
o
C
***It is set 80 for the MPB 80 burner