INSTALLATION
13
4.
INSTALLATION
4.1.
Hydraulic connections
The boiler is intended for connection with an open expansion vessel network. The boiler can be
connected also with closed expansion vessel, if it is equipped with an overheating serpentine
(optional).
The boiler is intended for maximum working temperature 90
o
C and maximum pressure 3 bar
for boilers up to 500 kW, and 4 bar for bigger boilers.
When connected with a closed expansion vessel, its volume must be chosen double to a similar
installation on liquid or gas fuel.
If a connection pipe is not used, it must be sealed before water fill!
Legend
T1 Outlet
T2 Return
T3 Chimney pipe
T4 Discharge valve connection
T5 Safety kit connection
T6 Additional safety connection
4.2.
Safety features
The boiler equipment includes a safety kit, which shall be connected to the corresponding
connection pipe T5. The kit consists of a safety valve, an air relief valve and a
thermomanometer. Bigger boilers are equipped with two or more safety valves.
Additional safety equipment can be mounted at the
connection pipe T6. This can be a dual safety valve
(pressure and temperature) or a cooling valve.
Alternatively this pipe can be used for connection
with the expansion vessel.
Fig 5.
Boiler safety kit