11.1  Remote switch contacts  IN0, IN1 

 
Terminals IN0 and IN1 on the Ecopower PCB inside the air 
curtain can be used to provide different control strategies 
using remote volt-free contacts (see Fig 9). This could be to 
provide remote On/Off from a timer or BMS Digital/Output 
contact, to work with a door switch or for simple weather 
compensation control to disable heating when outdoor air 
temperatures become warmer. Table 4 describes the 
different functions: 
 
 

Function 

IN0

 

Notes 

 

 

 
 

Remote 

On/Off 

(INHIBIT) 

 

Unit operates 
normally in 
MANUAL Mode or 
AUTO Mode 
from the Remote 
Control 

Unit switches off 
after 15s, with fan 
run-on at Medium 
fan speed if 
DIP 2 = OFF 

Use the Remote Control to set up unit and 
then hide it away if required. * 
 
On/Off is then done via IN0 using a remote 
volt-free contact. 

 

Function 

IN1

 

DIP 4 

IN0 

Notes 

 

 

 

Door 

Switch 

Control 

After 30s the 
heating is disabled 
and the fan goes to 
low speed 

Unit operates 
normally in 
MANUAL Mode or 
AUTO Mode 
from the Remote 
Control 

 
 
 

ON 

 
 
 
 
 
   

 

 
 
 
   

 

 Door Open:- 
   Normal Control 
 
 Door Closed:- 
   Heating Off 
   Low Fan Speed 

 
 

Summer 

 

Winter 

Unit operates 
normally in 
MANUAL Mode or 
AUTO Mode 
from the Remote 
Control 

COLD DAY

 

Heating is disabled 
straight away, 
Fan speeds 
operate normally 
from the Remote 
Control 

WARM DAY

 

 
 
 

OFF 

Simple weather 
compensation control 
using an outdoor air 
thermostat with volt free 
contacts 
(see Section 11.3) 

 
 
 
 
 
 
 
 
 
 
 
 

 

11. EXTERNAL 

CONTROLS 

Fig 9 

Table 4 

WARNING: 

Do not apply any voltage to terminals IN0 and IN1 as this will damage the Ecopower 
PCB inside the air curtain.

NOTE: 

Wire volt-free, remote switch contacts to 2-way screw terminals IN0 and IN1 using 2-core 
cable. 

NOTE: 

The Ecopower Remote Control must stay plugged-in for the air curtain to keep working. 
An optional plug-in EEPROM is available from Thermoscreens so the Remote Control can be un-
plugged and the air curtain stay working. Visit the Thermoscreens website for details. 

Содержание HX1000A

Страница 1: ...T9901008 1 1 UK v9 Page 1 AIR CURTAIN PHV SURFACE MOUNTED RANGE INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS English...

Страница 2: ...IGURATION 12 14 FAN SPEED SELECTION 13 15 REMOTE CONTROL OPERATION 13 16 COMMISSIONING THE SYSTEM 15 17 SIGN OFF 15 18 FAULT CONDITIONS 16 19 SERVICE MAINTENANCE 17 20 WARRANTY 18 APPENDIX 1 Dimension...

Страница 3: ...ng installed see Section 3 Specifications Models operating on a 3 phase electrical supply see Section 3 Specifications require a neutral connection 3N A 25mm size cable gland or conduit connector of I...

Страница 4: ...ide a building and located horizontally over a doorway They must not be installed on the outside of a building or built into a cabinet or recessed in any way Please complete the following details for...

Страница 5: ...re supplied loose to be fitted during installation Supplied with 6m RJ Control Cable Outdoor Air Thermostat Optional supplied by Installer Wall Brackets and M6 Fixing Bolts 3 port control valve for wa...

Страница 6: ...ckets to the rear face of the unit as shown in Fig 2 using the M6 fixing bolts supplied Step 2 Drill fixing points in the wall referring to Appendix 1 for correct positioning Step 3 Screw in the top w...

Страница 7: ...imum heat output of the air curtain are given in Table 2 below Air Curtain Water Flow Rate l min at 82 71 C Water Pressure Drop kPa PHV1000W 2 row 12kW 15 6 5 0 PHV1500W 2 row 18kW 23 4 9 5 PHV2000W 2...

Страница 8: ...e 8 1 1 Remove air inlet grilles Using a Pozi No 1 screwdriver remove each grill with its filter To remove insert screwdriver into the elongated hole at the bottom corner of the grille see Fig 5 and t...

Страница 9: ...e and secure back case to switch box using 2 mounting screws not supplied see Fig 8 Step 3 Connect the RJ plug to the RJ socket on the PCB in the remote control Step 4 Refit the front case On the back...

Страница 10: ...itch Control After 30s the heating is disabled and the fan goes to low speed Unit operates normally in MANUAL Mode or AUTO Mode from the Remote Control ON Door Open Normal Control Door Closed Heating...

Страница 11: ...to 2 way terminal IN1 on the Ecopower PCB see Fig 11 On the Ecopower PCB set DIP 4 to OFF as per Table 4 see Section 11 1 Remote switch contacts IN0 IN1 For master slave control plug and connect unit...

Страница 12: ...r curtain is used to measure air temperature Set DIP 3 to ON in the air curtain that will be the master unit DIP 3 OFF Air curtains in master slave systems all act independently Air sensor thermistors...

Страница 13: ...ith average acoustic characteristics as defined in CIBSE Guide B5 reverberation time 0 7s at 1kHz and a room size equivalent to 8 air changes per hour ac h Care needs to be taken when selecting air cu...

Страница 14: ...ct heating level from zero to half heat to full heat by stepping up or down with the heating level controls The heating level scale shows the level selected Automatic mode Heat output is controlled au...

Страница 15: ...curtain must be given supervision and instruction by the person responsible for their safety concerning the safe use of the unit and to understand any hazards involved Children and those with reduced...

Страница 16: ...and after 30 seconds the LEDs on the remote control will stop flashing and the status LED on the Ecopower PCB in the air curtain will flash green 18 2 Fuses In the event of an electrical fault intern...

Страница 17: ...Check within the unit to ensure all electrical connections and crimped terminals are tight and that all cables are in good condition Refit air inlet grilles after servicing Reconnect electrical supply...

Страница 18: ...has been taken in compiling these instructions to ensure they are correct Thermoscreens Ltd disclaims all liability for damage resulting from any inaccuracies and or deficiencies in this documentatio...

Страница 19: ...AIR IN AIR OUT 377 A B D C Remote control connection interface Entry point for electrical supply and controls Rp in BSP LPHW connections G G mm 255 B C D E F G 1746 2296 800 1400 1896 948 198 173 200...

Страница 20: ...eed Med speed Low speed 0V Fan 2 Fan 1 J17 ECO Power CVR1008 9 10 9 8 7 6 5 4 3 2 1 L3 N L2 L1 J10 J16 J12 J5 J6 J11 R 0 10V J14 Th EEPROM F2 F1 J9 Alarm Healthy Black rectangle is moveable head of DI...

Страница 21: ...Black rectangle is moveable head of DIP switch A1 A2 13NO 14NO 1 2 3 4 5 6 CONTACTOR 230V AC Coil Brown Black Grey TERMINAL BLOCK L1 L2 L3 N E L1 L2 L3 N E 400V 3ph 50Hz Brown Brown Blue Blue Summer W...

Страница 22: ...BLOCK L1 L2 L3 N E L1 L2 L3 N E 400V 3ph 50Hz Brown Brown Blue Blue 85 C Auto Thermal Trip x2 Summer Winter or Door Contact First Stage Heating bottom elements Second Stage Heating top elements Black...

Страница 23: ...J16 J12 J5 J6 J11 R 0 10V J14 Th EEPROM F2 F1 J9 Black rectangle is moveable head of DIP switch Grey Orange White Blue Green Yellow Brown 3 PORT VALVE 1 2 3 4 E Black White Summer Winter or Door Conta...

Страница 24: ...emote Control Switch 8 7 6 5 4 3 2 1 1 2 3 4 0 I F1 5A White Black Blue Medium speed High speed Red Red Blue Black Fan Motor 1 0 1 2 3 4 1 White COMMON Black High Blue Red Low Yellow Capacitor 7 5 F R...

Страница 25: ...ed Relevant EC Council the Machinery Directive 2006 42 EC Directives the Low Voltage Directive 2006 95 EC the Electromagnetic Compatibility Directive 2004 108 EC the Energy related Products Directive...

Отзывы: