Kit Contents
Tools Required
Receiving, Storing and Handling
1. Inspect materials for damage incurred during shipping.
2. Report damages to the carrier for settlement.
3. Identify parts against the packing list to ensure the proper type and
quantity has been received.
4. Store in a dry location.
Installation Precautions
• To minimize the potential for arcing and fire caused by product damage
or improper installation use ground-fault protection.
• Installation must comply with Thermon requirements and be installed
in accordance with the applicable national and local codes.
• Component approvals and performance ratings are based on the use
of Thermon specified parts only.
• De-energize all power sources before opening enclosure.
• Keep ends of heating cable and kit components dry before and during
installation.
• Individuals installing these products are responsible for complying with
all applicable safety and health guidelines. Proper personal protective
equipment, or PPE, should be utilized during installation. Contact
Thermon if you have any additional questions
The Specific Conditions of Use are:
1. The kits are intended for use with FM Approved BSX, HTSX, KSX, RSX,
TSX, VSX-HT, HPT, and FP heat tracing cables.
2. The equipment can only be used in areas of low impact risk.
3. Avoid electrostatic charge. Clean only with a damp cloth.
4. The maximum operating voltage rating is limited to 275 VAC when
wiring is done using the terminal block option
5. Minimum installation Temperature for terminators that use the wei-
dmuller terminals is -50°C.
Terminator
TM
ZE-B Beacon
Item
Quantity
Description
1
1
Expediter Assembly
Grommet Compressor
Grommet
Support Base with O-Ring
2
1
Light Module Cover
3
1
Banding Guide
4
1
Banding
5
1
LED Light Module
Order Separately
SCTK Connection Termination Kits (per cable)
SCTK-1
for BSX, RSX, VSX-HT
SCTK-2
for KSX, HTSX
SCTK-3
for FP, HPT
Item
Quantity
Description
1
3
Splice Connection Boots
2
2
Small Crimps
3
1
Large Crimp
4
2
Small Crimp Insulators
5
2
Silicone Caps
6
3
Ground Sleeves (not used with ZE-B Kits)
7
1
RTV Tube
8
1
GRW-G (FP and HPT only)
IP66/Type 4X -60°C ≤ Ta ≤ +45°C, T6, T85°C
-60°C ≤ Ta ≤ +55°C, T5, T85°C
Ordinary & Hazardous Locations
Class I, Division 2, Groups A, B, C, & D, T6...T5
Class II, Division 2, Groups F & G, Class III
Class I, Zone 1, AEx eb mb IIC T6...T5, Gb
09.2238691, -G, -S, Ex eb mb IIC T6...T5, Gb
Zone 21 AEx tb IIIC T85°C, Db
FMG 18.0026X Ex eb mb IIC T6...T5, Gb Ex tb IIIC T85°C, Db
Certifications/Approvals
Note:
Crimp Tool - Ideal 30-429 or factory approved
alternate.
1725 II 2 GD Ex eb mb IIC T6...T5, Gb Ex tb IIIC T85°C, Db FM 18ATEX0065X
Dimensions
210 mm
(8.25")
76 mm
(3")
89 mm
(3.5")
64 mm
(2.5")
1
2
4
3
5
2
4
3
5
6
1
7
8
Order Separately
SCTK Terminal Block Connection Kits (per cable)
SCTK-1TB
for BSX, RSX, VSX-HT
SCTK-2TB
for KSX, HTSX
SCTK-3TB
for FP, HPT
Item
Quantity
Description
1
1
Terminal Block
2
1
Terminal Block Mounting Screw
3
1
Splice Connection Boot
4
1
RTV Tube
5
1
GRW-G Grommet (SCTK-3TB only)
2
4
3
5
1